12 4 3 x y, Selection procedure, 50xp corner weights (in pounds) – Carrier 13 50XP User Manual

Page 10

Advertising
background image

10

50XP

I Determine cooling and heating requirements at design

conditions:
Given:
Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh
Sensible Heat Capacity (SHC). . . . . . . . . . . . 26,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . . 15,000 Btuh
Condenser Entering Air Temperature . . . . . . . . . . . . 95°F
Indoor-Air Temperature. . . . . . . . . . . 80°F edb, 67°F ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . 1200 cfm
External Static Pressure . . . . . . . . . . . . . . . . . . . 0.2 in. wg
Electrical Characteristics . . . . . . . . . . . . . . . . . . .230-1-60

II Select unit based on required cooling capacity.

Enter Cooling Capacities table at condenser entering
temperature of 95°F. The 036 unit at 1225 cfm and 67°F
ewb (entering wet bulb) will provide a total capacity of
36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC
correction, if required, using Note 4 under Cooling
Capacities tables.

III Select electric heat.

The required heating capacity is 15,000 Btuh (given).
Determine the electric heat capacity in kW.
15,000 Btuh
3414 Btuh/kW

Enter the Electric Heater Packages table for 208/240,
single-phase, 036 unit. The 5-kW heater at 240v most

closely satisfies the heating required. To calculate kW at
208v, multiply the heater kW by multiplication factor 0.75
found in the Wattage Multiplication Factors table.
5 kW x 0.75 = 3.75 kW
3.75 kW x 3414 Btuh/kW = 12,802.50 Btuh

IV Determine fan speed and power requirements at design

conditions.
Before entering the air delivery tables, calculate the total
static pressure required. From the given, Filter Pressure
Drop table, and the Accessory Electric Heat Pressure Drop
table, find:
Wet coil pressure drop

0.032 in. wg

External static pressure

0.200 in. wg

Filter

0.130 in. wg

Total static pressure

0.362 in. wg

Enter the table for Dry Coil Air Delivery — At 0.362 in. wg
external static pressure and NOM speed pin selection, the
motor delivers 1235 cfm.

V Select unit that corresponds to power source available.

The Electrical Data table shows that the unit is designed to
operate at 208/230-1-60.

= 4.4 kW of heat required

Selection Procedure

Small Base

Large Base

Model 50XP

024

030

036

042

048

060

Corner Weight #1

69

69

74

87

92

99

Corner Weight #2

53

53

57

67

71

77

Corner Weight #3

83

83

88

104

110

119

Corner Weight #4

138

138

147

174

183

198

Total Weight

343

343

366

433

456

492

50XP Corner weights (In Pounds)

1

2

4

3

x

y

50XP

Advertising