Performance data (cont), Standard ecm indoor motor, Cooling capacities – Carrier 13 50XP User Manual

Page 13

Advertising
background image

13

50XP

Performance data (cont)-

Standard ECM Indoor Motor

COOLING CAPACITIES

50XP048 COOLING PERFORMANCE TABLE

Temp (F)

Outdoor Air

Entering

Condenser

Evaporator Air—CFM/BF

1260/0.06

1400/0.06

1600/0.08

Evaporator Air — Ewb (F)

62

63*

67

72

62

63*

67

72

62

63*

67

72

75

TC

45.0

45.8

49.6

54.7

46.7

47.3

51.2

56.3

48.1

48.7

52.5

57.8

SHC

39.3

32.0

33.4

27.2

42.6

34.3

35.8

28.9

45.8

36.8

38.4

30.6

kW

3.4

3.4

3.4

3.4

3.4

3.4

3.4

3.5

3.4

3.4

3.4

3.5

85

TC

42.8

43.6

47.2

52.1

44.3

44.9

48.6

53.5

45.6

46.1

49.9

54.8

SHC

38.2

30.9

32.3

26.2

41.3

33.2

34.7

27.7

44.3

35.5

37.3

29.4

kW

3.7

3.7

3.8

3.8

3.7

3.7

3.8

3.8

3.8

3.8

3.8

3.8

95

TC

40.6

41.3

44.7

49.4

41.8

42.4

46.0

50.7

44.2

43.7

47.0

51.8

SHC

36.9

29.8

31.2

25.2

39.9

32.0

33.6

26.7

43.0

34.6

36.1

28.3

kW

4.1

4.1

4.2

4.2

4.1

4.1

4.2

4.2

4.2

4.1

4.2

4.2

105

TC

38.2

38.9

42.1

46.4

39.6

39.8

43.1

47.6

41.5

40.8

44.0

48.5

SHC

35.7

28.7

30.1

24.0

38.3

30.7

32.3

25.5

40.0

33.2

34.8

27.0

kW

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.7

4.6

4.6

4.6

4.7

115

TC

35.7

36.3

39.3

43.3

38.2

37.1

40.1

44.2

38.7

37.9

40.8

45.0

SHC

34.4

27.5

28.9

22.9

35.7

29.5

31.0

24.3

38.2

31.8

33.5

25.8

kW

5.0

5.0

5.1

5.1

5.1

5.0

5.1

5.1

5.1

5.1

5.1

5.1

125

TC

33.4

33.4

36.2

39.4

34.6

34.1

36.9

40.5

36.1

34.8

37.5

41.2

SHC

32.1

26.2

27.6

21.5

33.8

28.2

29.7

22.9

35.6

30.2

31.9

24.4

kW

5.6

5.6

5.6

5.7

5.6

5.6

5.6

5.6

5.6

5.6

5.6

5.6

50XP060 COOLING PERFORMANCE TABLE

Temp (F)

Outdoor Air

Entering

Condenser

Evaporator Air—CFM/BF

1500/0.004

1750/0.007

2000/0.01

Evaporator Air — Ewb (F)

62

63*

67

72

62

63*

67

72

62

63*

67

72

75

TC

57.2

58.2

62.4

68.1

58.8

59.7

64.0

69.8

60.0

60.8

64.9

70.8

SHC

49.4

47.9

41.6

33.8

53.6

51.8

44.5

35.4

57.6

55.4

47.1

36.8

kW

4.1

4.1

4.2

4.2

4.2

4.3

4.3

4.4

4.4

4.4

4.5

4.6

85

TC

54.7

55.6

59.7

65.2

56.2

57.0

61.1

66.6

57.4

58.1

61.9

67.4

SHC

48.2

46.7

40.4

32.6

52.4

50.5

43.2

34.2

56.3

54.2

45.8

35.6

kW

4.5

4.5

4.6

4.7

4.7

4.7

4.8

4.9

4.8

4.9

5.0

5.0

95

TC

52.2

53.0

56.9

62.0

53.5

54.3

58.0

63.2

55.0

55.3

58.7

64.1

SHC

47.0

45.4

39.2

31.4

51.1

49.2

41.9

32.9

55.0

52.9

44.5

34.4

kW

5.0

5.0

5.1

5.2

5.1

5.2

5.3

5.3

5.2

5.3

5.5

5.5

105

TC

49.4

50.2

53.8

58.7

50.7

51.4

54.8

59.6

52.5

52.4

55.4

60.2

SHC

45.7

44.1

37.9

30.1

49.8

47.9

40.6

31.6

52.5

51.6

43.2

33.0

kW

5.5

5.6

5.6

5.7

5.7

5.7

5.8

5.9

5.8

5.8

6.0

6.1

115

TC

46.5

47.2

50.5

55.0

48.1

48.3

51.3

56.8

49.7

49.7

51.8

57.0

SHC

44.3

42.7

36.4

28.7

48.1

46.6

39.2

30.6

49.7

49.7

41.8

31.7

kW

6.1

6.2

6.2

6.3

6.2

6.3

6.4

6.4

6.4

6.4

6.6

6.6

125

TC

43.3

43.9

46.7

52.2

45.2

45.1

47.4

52.5

46.4

46.4

47.9

52.2

SHC

42.8

41.2

34.9

27.8

45.2

45.1

37.6

28.9

46.4

46.4

40.2

29.7

kW

6.7

6.8

6.8

6.8

6.8

6.9

7.0

7.0

7.0

7.0

7.2

7.2

LEGEND

BF

Bypass Factor

Ewb

Entering Wet-Bulb

kW

Total Unit Power Input

SHC

Sensible Heat Capacity (1000 Btuh)

TC

Cooling Capacity (1000 Btuh)

ECM

Electronic Computated Motor

*

TVA Conditions (75°F Entering Dry Bulb)

NOTES:
1. Ratings are net; they do account for the effects

of the evaporator-fan motor power and heat.

2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

4. The SHC is based on 80°F Edb (Entering dry bulb) air temperature

through Evaporator coil. Below 80°F Edb, subtract (Correction Factor x
CFM) from SHC. Above 80°F Edb, add (Correction Factor x CFM) to
SHC. Correction Factor = 1.10 x (1 – BF) x (Edb – 8)

sensible capacity (Btuh)

t

= t

؊

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

؊

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

Advertising