Performance data (cont)

ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)

MULTIPLICATION FACTORS

Example: 15.0 kW (at 240v) heater on 208 v

= 15.0 (.75 mult factor)
= 11.25 capacity at 208 v

UNIT50XP

PRESSURE DROP

024-036

0.20

042-060

0.25

HEATER kW

RATING

VOLTAGE

DISTRIBUTION

MULTIPLICATION

FACTOR

240

200
208
230
240

.69
.75
.92

1.00

ELECTRIC HEAT PRESSURE DROP TABLES

Small Cabinet: 024-036

Large Cabinet: 042-060

STATIC

CFM

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

5 kW

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.02

0.04

0.06

0.07

7.5 kW

0.00

0.00

0.00

0.00

0.00

0.00

0.02

0.03

0.05

0.07

0.08

0.09

10 kW

0.00

0.00

0.00

0.00

0.00

0.02

0.04

0.06

0.07

0.09

0.10

0.11

15 kW

0.00

0.00

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.18

STATIC

CFM

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

2400

2500

5 kW

0.00

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

7.5 kW

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

10 kW

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

15 kW

0.00

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

20 kW

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

FILTER PRESSURE DROP (In. wg)

FILTER SIZE

CFM

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

20 X 20 X 1

0.05

0.07

0.08

0.10

0.12

0.13

0.14

0.15

20 X 24 X 1

0.09

0.10

0.11

0.13

0.14

0.15

0.16

24 X 30 X 1

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.18