Accessory dimensions, 50xp – Carrier 13 50XP User Manual

Page 9

Advertising
background image

9

50XP

Accessory dimensions

UNIT SIZE

ODS CATALOG NUMBER

A

in. [mm]

B

in. [mm]

C

in. [mm]

D

in. [mm]

50XP024-036

CPRFCURB006A00

8 [203]

11 [279]

16-1/2 [419]

28-3/4 [730]

CPRFCURB007A00

14 [356]

11 [279]

16-1/2 [419]

28-3/4 [730]

50XP042-060

CPRFCURB008A00

8 [203]

16-3/16 [411]

17-3/8 [441]

40-1/4 [1022]

CPRFCURB009A00

14 [356]

16-3/16 [411]

17-3/8 [441]

40-1/4 [1022]

C00076

Gasket around

outer edge

Insulated
deck pan

Gasket around

duct

S/A

R/A

HVAC unit

base

*Gasketing

outer flange

Flashing field

supplied

Roofing material

field supplied

Cant strip

field supplied

*Provided with roofcurb

Roof

Duct work

field supplied

Insulation (field

supplied)

Roofcurb*

Wood nailer*

Gasketing

inner flange*

Screw

(NOTE A)

Roof Curb for Small Cabinet

Note A: When unit mounting screw is used,

retainer bracket must also be used.

HVAC unit

base

*Gasketing

outer flange

Flashing field

supplied

Roofing material

field supplied

Cant strip

field supplied

*Provided with roofcurb

Roof

Duct work

field supplied

Insulation (field

supplied)

Roofcurb*

Wood nailer*

Gasketing

inner flange*

Screw

(NOTE A)

Roof Curb for Large Cabinet

Note A: When unit mounting screw is used,

retainer bracket must also be used.

A

B Typ.

Supply opening
(B x C)

Long

Support

D

44

5

/

16

"

(1125.5mm)

Return opening

(B X C)

Insulated
deck pan

Short

Support

C Typ.

NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code

for hurricane or seismic conditions. This bracket is available through Micrometl.