Guide specifications – Carrier 13 50XP User Manual

Page 23

Advertising
background image

23

50XP

Packaged Electric Cooling Units
Constant Volume Application

HVAC Guide Specifications
Size Range: 2 to 5 Tons, Nominal Cooling
Carrier Model Number: 50XP
Part 1—General
SYSTEM DESCRIPTION

Outdoor rooftop or ground mounted, electric cooling
unit utilizing a hermetic compressor for cooling duty
and optional electric heating. Unit shall discharge sup-
ply air vertically or horizontally as shown on contract
drawings. Condenser fan/coil section shall have a
draw-thru design with vertical discharge for minimum
sound levels.

QUALITY ASSURANCE

A. Unit shall be rated in accordance with ARI Standards

210/240-94 and 270-95.

B. Unit shall be designed in accordance with UL Standard

1995.

C. Unit shall be manufactured in a facility registered to

ISO 9001 manufacturing quality standard.

D. Unit shall be UL listed and c-UL certified as a total

package for safety requirements.

E. Roof curb shall be designed to conform to NRCA Stan-

dards.

F. Insulation and adhesives shall meet NFPA 90A re-

quirements for flame spread and smoke generation.

G. Cabinet insulation shall meet ASHRAE Standard 62P.

DELIVERY, STORAGE AND HANDLING

Unit shall be stored and handled per manufacturer’s

recommendations.

Part 2 — Products
EQUIPMENT

A. General:

Factory-assembled, single-piece, cooling unit. Con-
tained within the enclosure shall be all factory wiring,
piping, controls, refrigerant charge (R-410A), and spe-
cial features required prior to field start-up.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of phosphated,

zinc-coated, pre-painted steel capable of withstand-
ing 500 hours of salt spray.

2. Normal service shall be through a single removable

cabinet panel.

3. The unit shall be constructed on a rust proof base-

pan that has an externally trapped, integrated sloped
drain pan.

4. Evaporator fan compartment top surface shall be in-

sulated with a minimum 1/2-in. thick, flexible fiber-
glass insulation, coated on the air side and retained
by adhesive and mechanical means. The evaporator
wall sections will be insulated with a minimum
semi-rigid foil-faced board capable of being wiped
clean. Aluminum foil-faced fiberglass insulation
shall be used in the entire indoor air cavity section.

5. Unit shall have a field-supplied condensate trap.

C. Fans:

1. The evaporator fan shall be direct-drive variable

speed motor and control, as shown on equipment
drawings.

2. Fan wheel shall be made from steel, and shall be

double-inlet type with forward curved blades with
corrosion resistant finish. Fan wheel shall be dy-
namically balanced.

3. Condenser fan shall be direct drive propeller type

with aluminum blades riveted to corrosion resistant
steel spiders, be dynamically balanced, and dis-
charge air vertically.

D. Compressor:

1. Fully hermetic compressors with factory-installed

vibration isolation.

2. Scroll compressors shall be standard on all units.

E. Coils:

Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless copper
tubes with all joints brazed. (Copper/copper and vinyl-
coated construction available as option.) Tube sheet
openings shall be belled to prevent tube wear.

F. Refrigerant Metering Device:

Refrigerant metering device shall be of the TXV type.

G. Filters:

Filter section shall consist of field-installed, throw-
away, 1-in. thick fiberglass filters of commercially
available sizes.

H. Controls and Safeties:

1. Unit controls shall be complete with a self-con-

tained low voltage control circuit.

2. Units shall incorporate an internal compressor pro-

tector that provides reset capability.

3. Unit shall provide High and Low/Loss-of-Charge

Pressure Safety Protection.

I. Operating Characteristics:

1. Unit shall be capable of starting and running at

125°F ambient outdoor temperature, exceeding
maximum load criteria of ARI Standard 210.

2. Compressor with standard controls shall be capable of

operation down to 55° F ambient outdoor temperature.

3. Indoor Fan on/off delay profile is selected (for cool-

ing) on the Easy Select™ Board.

J. Electrical Requirements:

All unit power wiring shall enter the unit cabinet at a

single location.

K. Motors:

1. Compressor motors shall be of the refrigerant-

cooled type with line-break thermal and current
overload protection.

2. All fan motors shall have permanently lubricated

bearings, and inherent, automatic reset, thermal
overload protection.

3. Condenser fan motor shall be totally enclosed.