DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)

MODE # MODE NAME

7

Delay at start-up active

8

2nd cooling setpoint active

9

Setpoint reset active

10

Demand limit active

11

Ramp loading active

12

Low entering water temperature
protection in heating mode

13,14

Low suction temperature protection

15,16

Low discharge superheat protection

17,18

High pressure protection

19,20

Not used

21

Heat reclaim active

22

Evaporator heater active

23

Evaporator pump reversal active

24

Periodic evaporator pump start-up

25

Low night-time capacity

26

Unit under SM control

27

Master/slave link active

DESCRIPTION

The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.
The delay is configured in the User1 configuration menu.

The second cooling setpoint is active. See section 5.7.1

In this mode, the unit uses the reset function to adjust the leaving or entering water temperature setpoint. See
section 5.7.2.

In this mode, the capacity at which the unit is allowed to operate is limited. See section 5.8.

Ramp loading is active. In this mode, the controlled high or low water temperature value (in °C/min) in heating mode
is limited to a preset value in order to prevent compressor overload. The ramp function must be configured (see
User1 configuration menu). The ramp values can be modified (see setpoint menu).

The unit is in heating mode and the temperature of the evaporator leaving water is lower than the lesser of the two
cooling setpoints. A capacity stage is removed. This mode only applies to heat pumps.

13 = circuit A & 14 = circuit B. Protection for evaporator suction low temperature circuit is active. In this mode, circuit
capacity is not authorised to rise if the unit is in cooling mode, and saturated suction temperature in the circuit is
lower by more than 13°C at the leaving chilled water and lower than the frost protection threshold.

15 = circuit A & 16 = circuit B.
In this mode the circuit capacity is shut down by pumpout and not allowed to restart, when the low superheat alarm
conditions are satisfied. During the shutdown/start-up sequence, mode 15 or 16 is active. See descriptions for
alarms 48 and 49.

17 = circuit A & 18 = circuit B. The circuit is in high pressure protection mode because the HP protection threshold
has been exceeded. The circuit capacity is not authorised to rise and any slave compressor can be stopped in order
to prevent a high pressure break.

Circuit A or circuit B operates in heat reclaim mode and not in standard cooling mode (pumpdown phase is
activated).

Mode active if risk of frost exists.

Two evaporator water pumps installed on the unit and pump reversal is active. See section 5.3

The unit is shut down and is started every day at 14:00 hours for 2 seconds. This function must be configured in the
User1 menu. See sections 5.3 and 4.5.7.3.

Unit capacity is limited. The period when this mode starts, as well as the limited capacity in night-time mode are
controlled in Client1 menu.

Unit is under control of a System Manager (FSM or CSM III).

Unit is connected to a secondary unit by a master slave link and either:
- the unit is configured as a master and this master is operating, or
- the unit is configured as a slave and this slave is operating.

4.5.2 - Description of the Temperatures menu

TEMPERATURES MENU [2]

ITEM

FORMAT UNITS

COMMENTS

0

±nn.n

°C

Evaporator entering water temperature

1

±nn.n

°C

Evaporator leaving water temperature

2[1]

±nn.n

°C

Condenser entering water temperature

3[1]

±nn.n

°C

Condenser leaving water temperature

4[1]

±nn.n

°C

Reclaim condenser entering water temperature

5[1]

±nn.n

°C

Reclaim condenser leaving water temperature

6

±nn.n

°C

Saturated discharge temperature circuit A

7

±nn.n

°C

Saturated suction temperature circuit A

8

±nn.n

°C

Suction temperature compressor A1

9

±nn.n

°C

Superheat circuit A

10[1]

±nn.n

°C

Saturated discharge temperature circuit B

11[1]

±nn.n

°C

Saturated suction temperature circuit B

12[1]

±nn.n

°C

Suction temperature compressor B1

13[1]

±nn.n

°C

Superheat circuit B

14[1]

±nn.n

°C

Outdoor temperature

15[1]

±nn.n

°C

Water loop temperature, master/slave assembly

Legend
1

This item is displayed in certain unit configurations only

2

Access to this menu is read-only.

4.5.3 - Description of the Pressures menu

PRESSURES MENU [2]

ITEM

FORMAT

UNITS

COMMENTS

0

nnnn

kPa

Discharge pressure circuit A

1

nnnn

kPa

Suction pressure circuit A

2

nnnn

kPa

Differential oil pressure compressor A1

3

nnnn

kPa

Discharge pressure circuit B

4

nnnn

kPa

Suction pressure circuit B

5

nnnn

kPa

Differential oil pressure compressor B1

6[1]

nnnn

kPa

Differential oil pressure compressor A2

7[1]

nnnn

kPa

Differential oil pressure compressor A3

8[1]

nnnn

kPa

Differential oil pressure compressor A4

9[1]

nnnn

kPa

Differential oil pressure compressor B2

10[1]

nnnn

kPa

Differential oil pressure compressor B3

11[1]

nnnn

kPa

Differential oil pressure compressor B4

12[1]

nnnn

kPa

Pumpdown pressure, heat reclaim, circuit A

13[1]

nnnn

kPa

Pumpdown pressure, heat reclaim, circuit B

Legend
1

This item is displayed in certain unit configurations only.

2

Access to this menu is read-only