Carrier PRO-DIALOG 30GK User Manual

Page 35

Advertising
background image

35

ALARM CODE DESCRIPTIONS

Code

Alarm name

Action

Pumpdown

Reset type

Probable cause

101

DGT fault, compressor A1

Circuit A shut down

No

Manual

Hot gas thermostat contact open

102

Starter Guard fault compressor A1

Circuit A shut down

No

Ditto

Crankcase heater fault and open motor current
fault detection board contact

201

DGT fault, compressor A2

Compressor A2 shut down

Ditto

Hot gas thermostat contact open

202

Starter Guard fault compressor A 2

Compressor A2 shut down

Ditto

Crankcase heater fault and open motor current
fault detection board contact

301

DGT fault, compressor A3

Compressor A3 shut down

Ditto

Hot gas thermostat contact open

302

Starter Guard fault compressor A 3

Compressor A3 shut down

Ditto

Crankcase heater fault and open motor current
fault detection board contact

401

DGT fault, compressor A4

Compressor A4 shut down

Ditto

Hot gas thermostat contact open

402

Starter Guard fault compressor A 4

Compressor A4 shut down

Ditto

Crankcase heater fault and open motor current
fault detection board contact

501

DGT fault, compressor B1

Circuit B shut down

No

Ditto

Hot gas thermostat contact open

502

Starter Guard fault compressor B1

Circuit B shut down

No

Ditto

Crankcase heater fault and open motor current
fault detection board contact

601

DGT fault, compressor B2

Compressor B2 shut down

Ditto

Hot gas thermostat contact open

602

Starter Guard fault compressor B 2

Compressor B2 shut down

Ditto

Crankcase heater fault and open motor current
fault detection board contact

701

DGT fault, compressor B3

Compressor B3 shut down

Ditto

Hot gas thermostat contact open

702

Starter Guard fault compressor B3

Compressor B3 shut down

Ditto

Crankcase heater fault and open motor current
fault detection board contact

801

DGT fault, compressor B4

Compressor B4 shut down

Ditto

Hot gas thermostat contact open

802

Starter Guard fault compressor B4

Compressor B4 shut down

Ditto

Crankcase heater fault and open motor current
fault detection board contact

6.4.1 - Compressor faults
6.4.1.1 - General
Each compressor is protected against multiple faults by two
digital inputs located on the control board. If one of these
inputs opens, it causes an immediate shutdown on the
compressor without any action from the basic board.

6.4.1.2 - Compressor protection devices
On PRO-DIALOG Plus units, compressors are individually
protected by the following devices connected to the digital
inputs on the compressor control board:

DGT (only for units with low-temperature option):
The discharge gas thermostat detects and protects the
compressor against abnormally high discharge temperatures.

Starter Guard:
This board patented by Carrier (also called AM board)
monitors both the compressor regime and the status of its
crankcase heaters which ensure correct lubrication when the
compressor starts.