ALARM CODE DESCRIPTIONS

Code

Alarm name

Description

Action

Pumpdown

Reset type

Probable cause

1

Evaporator leaving water thermistor fault

Thermistor outside range

Unit shut down

Yes

Auto

Thermistor or wiring fault or
bad connection

2

Evaporator entering water thermistor fault

Ditto

Unit shut down

Yes

Auto

Ditto

3

Condenser leaving water thermistor fault

Ditto

Heating mode: Unit shut down,

Yes

Auto

Ditto

if control on leaving water.
Cooling mode: no action

4

Condenser entering water thermistor fault

Ditto

Heating mode: Unit shut down,

-

Auto

Ditto

if control on entering water.
Cooling mode: no action

5

Heat reclaim entering water thermistor fault

Ditto

Unit with heat recalaim option:

-

Auto

Ditto

heat reclaim mode shut down,
unit changes over to standard
cooling mode. If not: no action

6

Heat reclaim leaving water thermistor fault

Ditto

None

-

Auto

Ditto

7

Outdoor temperature sensor fault

Ditto

Reset: normal setpoint used.

-

Auto, if temp. mea-

Thermistor faulty

Limitation or reset deactivated.

sured by sensor
returns to normal

8

CHWS (master/slave) fluid thermistor fault

Ditto

Deactivated

-

Ditto

Themistor faulty

9

Suction thermistor fault, compressor A1

Ditto

Circuit A shut down

Yes

Auto

Ditto

10

Suction thermistor fault, compressor B1

Ditto

Circuit B shut down

Yes

Auto

Ditto

11

External 0-10 V dc signal fault

Reset signal outside range

Reset: normal setpoint used

No

Auto

Signal incorrect, wiring error

Limitation or reset deactivated

12

Discharge pressure sensor fault, circuit A

Voltage transmitted by incorrect sensor Circuit A shut down

Yes

Auto

Sensor fault or wiring error

13

Discharge pressure sensor fault, circuit B

Ditto

Circuit B shut down

Yes

Auto

Ditto

14

Suction pressure sensor fault, circuit A

Ditto

Circuit A shut down

No

Auto

Ditto

15

Suction pressure sensor fault, circuit B

Ditto

Circuit B shut down

No

Auto

Ditto

16

Oil pressure sensor fault, compressor A1

Ditto

Circuit A shut down

No

Auto

Ditto

17

Oil pressure sensor fault, compressor B1

Ditto

Circuit B shut down

No

Auto

Ditto

18

Oil pressure sensor fault, compressor A2

Ditto

Compressor A2 shut down

-

Auto

Ditto

19

Oil pressure sensor fault, compressor B2

Ditto

Compressor B2 shut down

-

Auto

Ditto

20

Oil pressure sensor fault, compressor A3

Ditto

Compressor A3 shut down

-

Auto

Ditto

21

Oil pressure sensor fault, compressor B3

Ditto

Compressor B3 shut down

-

Auto

Ditto

22

Oil pressure sensor fault, compressor A4

Ditto

Compressor A4 shut down

-

Auto

Ditto

23

Oil pressure sensor fault, compressor B4

Ditto

Compressor B4 shut down

-

Auto

Ditto

24

Pumpdown pressure sensor fault, circuit A

Ditto

If circuit is in heat reclaim

-

Auto, if press. mea-

mode, it goes to cooling mode.

sured by sensor

If not, no action

returns to normal

25

Pumpdown pressure sensor fault, circuit B

Ditto

Ditto

-

Ditto

Ditto

26

Loss of communication with compressor board A1

Communication with the compressor

Circuit A shut down

No

Auto

Wiring fault, faulty module,

board is lost

incorrect module address

27

Loss of communication with compressor board A2

Ditto

Compressor A2 shut down

No

Auto

Ditto

28

Loss of communication with compressor board A3

Ditto

Compressor A3 shut down

No

Auto

Ditto

29

Loss of communication with compressor board A4

Ditto

Compressor A4 shut down

No

Auto

Ditto

30

Loss of communication with compressor board B1

Ditto

Circuit B shut down

No

Auto

Ditto

31

Loss of communication with compressor board B2

Ditto

Compressor B2 shut down

No

Auto

Ditto

32

Loss of communication with compressor board B3

Ditto

Compressor B3 shut down

-

Auto

Ditto

33

Loss of communication with compressor board B4

Ditto

Compressor B4 shut down

-

Auto

Ditto

34

Loss of communication with EXV board

Ditto

Unit shut down

No

Auto

Wiring bus faulty, incorrect
address or board faulty

35

Loss of communication with NRCP board

The board does not respond

Unit shut down, if heat reclaim mode No

Auto, if board is

NRCP board faulty

is selected

again detected

36

Loss of communication with fan board 1

Ditto

Unit shut down, if the number of

No

Auto

Wiring bus faulty, incorrect

fan stages per circuit is less than 3.

address or board faulty

If not, circuit A shut down

37

Loss of communication with fan board 2

Ditto

Circuit B shut down

No

Auto

Ditto

38

Loss of communication with 4xAI - 2xAO board 1

Ditto

Unit shut down or no action

No

Auto

Ditto, depending on
configuration

39

Loss of communication with 4xAI - 2xAO board 2

Ditto

Compressors or circuit shut down

No

Auto

Ditto, depending on
configuration

40

Pumpdown fault, circuit A

End of pumpdown conditions not

Circuit A shut down

No

Manual

EXV or sensor faulty

satisfied

41

Pumpdown fault, circuit B

Ditto

Circuit B shut down

No

Manual

Ditto

42

Evaporator frost protection

Unit operating: units shut down if

Unit shut down

No

Auto first time,

Low water flow or

temp. < defrost threshold.

then manual

thermistor defective

Unit shut down: if temp < threshold
and evaporator heater on for more
than 10 mins.

43

Low evaporator water flow rate.

Unit shut down

No

Manual

Water pump faulty

44

Low suction temperature, circuit A

Circuit operating: saturated suction

Circuit A shut down

No

Manual

Low charge, filter dirty

temp. < defrost threshold and < leaving

ot thermistor faulty

water -16°C for more than 10 mins.

45

Low suction temperature, circuit B

Ditto

Circuit B shut down

No

Manual

Ditto

46

High suction overheat, circuit A

EXV fully open

Circuit A shut down

Yes

Manual

Ditto

47

High suction overheat, circuit B

Ditto

Circuit B shut down

Yes

Manual

Ditto

48

Low suction overheat, circuit A

EXV in min. position, and circuit

Circuit A shut down

Yes

Manual

EXV or thermistor or

superheat below superheat setpoint

transducer defective

-5.5 K, saturated suction temp. above
MOP for 5 mins.

6.4 - Alarm codes

The following list gives a complete description of each alarm
code and its possible cause.