4.5.10 - Runtime menu description

RUNTIMES

RUNTIMES 1
[runtiMES 1]

RUNTIMES 2
[runtiMES 2]

MAINTENANCE

[MAintEnAnCE]

NOTE: The items in brackets show what is displayed on the
user interface.

4.5.10.1 - Description of the Runtimes 1 menu

RUNTIMES MENU [1]

iTEM # FORMAT

UNIT

COMMENTS

0

-

-

When selected this item
authorises return to the previous
menu

1

nnnn | M 10 | M100

hrs/10 or 100

Unit operating hours*

2

nnnn | M 10 | M100

hrs/10 or 100

Compressor A1 operating hours*

3 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor A2 operating hours*

4 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor A3 operating hours*

5 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor A4 operating hours*

6 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor B1 operating hours*

7 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor B2 operating hours*

8 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor B3 operating hours*

9 [1]

nnnn | M 10 | M100

hrs/10 or 100

Compressor B4 operating hours*

10

nnnn | M 10 | M100

-/10 or 100

Machine starts*

11

nnnn | M 10 | M100

-/10 or 100

Compressor A1 starts*

12 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor A2 starts*

13 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor A3 starts*

14 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor A4 starts*

15 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor B1 starts*

16 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor B2 starts*

17 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor B3 starts*

18 [1]

nnnn | M 10 | M100

-/10 or 100

Compressor B4 starts*

NOTES
1

This item is masked when not used

*

Certain values are divided by 10 or by 100, so that number of hours or start-
ups of less then 10 are displayed as 0.

When the value is divided by 10 or by 100 it is displayed in turn with “M 10” or
“M100”.

4.5.10.2 - Description of the Runtimes 2 menu

RUNTIMES MENU [2]

iTEM # FORMAT

UNIT

COMMENTS

0

-

-

When selected this item
authorises return to the previous
menu

1

nnnn | M 10 | M100

hrs/10 or 100

Pump #1 operating hours*

2

nnnn | M 10 | M100

hrs/10 or 100

Pump #2 operating hours*

3 [1]

nnnn | M 10 | M100

hrs/10 or 100

Condenser pump operating
hours

4 [1]

nnnn

-

Number of start-ups for the
compressor with the highest
number during the last hour

5

nnnn

-

Average number of compressor
start-ups/hour for the last 24
hours

4.5.10.3 - Maintenance menu description
To be active, the maintenance function must be preset in the
Service configuration.

ITEM # FORMAT

DESCRIPTION

0

MAintEnAnCE MEnu When selected this item authorises return to the

previous menu.

1 [1]

Accessible with the Service password.

2 [1]

For future use

3 [1]

For future use

4 [1]

ALErt

Water loop rate to low

5 [1]

nnn/ALErt

Next primary pump maintenance operation in nnn
days. 'ALErt' is displayed, when the delay before
maintenance has elapsed.

6 [1]

nnn/ALErt

Next secondary pump maintenance operation in
nnn days. 'ALErt' is displayed, when the delay
before maintenance has elapsed.

7 [1]

nnn/ALErt

Next water filter maintenance operation in nnn
days. 'ALErt' is displayed, when the delay before
maintenance has elapsed.

Legend