ALARM CODE DESCRIPTIONS

Code

Alarm name

Description

Action

Pumpdown

Reset type

Probable cause

49

Low suction overheat, circuit B

Circuit B shut down

Yes

Manual

Ditto

50

Low oil pressure, compressor A1

Oil pressure < min. threshold

Circuit A shut down

No

Manual

Compressor, crankcase
heater, pressure sensor or
EXV faulty, refrigerant
charge too high, low oil
charge

51

Low oil pressure, compressor B1

Ditto

Circuit B shut down

No

Manual

Ditto

52

Low oil pressure, compressor A2

Ditto

Compressor A2 shut down

Manual

Ditto

53

Low oil pressure, compressor B2

Ditto

Compressor B2 shut down

Manual

Ditto

54

Low oil pressure, compressor A3

Ditto

Compressor A3 shut down

Manual

Ditto

55

Low oil pressure, compressor B3

Ditto

Compressor B3 shut down

Manual

Ditto

56

Low oil pressure, compressor A4

Ditto

Compressor A4 shut down

Manual

Ditto

57

Low oil pressure, compressor B4

Ditto

Compressor B4 shut down

Manual

Ditto

58

Evaporator water flow control fault

1. Interlock not closed before end

Unit shut down.

No

Manual

Evaporator water flow fault

of start-up delay

Pump shut down

2. Pump shut down for 2 mins
and water flow contact closed

59

Low pressure fault, circuit A

Circuit operating, and suction pressure

Circuit A shut down

No

Auto first time,

Low refrigerant charge, EXV

below permitted threshold for more

then manual*

faulty or filter dirty

than 3 mins.

60

Low pressure fault, circuit B

Ditto

Circuit B shut down

No

Ditto

Ditto

61

Repeated high pressure load sheds, circuit A

More than 6 successive capacity load

None

No

Auto

Transducer faulty, condenser

sheds in the circuit due to exceeded

ent. air temp., evaporator ent.

high pressure

water temp. too high, cond.
blocked or fan flow rate too
low

62

Repeated high pressure load sheds, circuit B

Ditto

Ditto

Ditto

Ditto

63

High pressure switch not reset or reverse compressor

The high pressure switch has not been

Circuit A shut down

No

Manual

The high pressure switch has

rotation, circuit A

reset after a high pressure cut-out,

not been reset, poor electrical

or the lead compressor does not work

connection of lead compr.

64

High pressure switch not reset or reverse compressor

Ditto

Circuit B shut down

No

Manual

Ditto

rotation, circuit B

65

Control box thermostat fault

Sensor overheat

Unit shut down

Manual

Control box poorly
ventilated

66

Loss of communication with System Manager

Units controlled by SM, and

Unit operates in autonomous mode

Auto

CCN network fault

communication with the module over
2 mins. faulty

67

Loss of communication with the master or slave

Master/slave connection interrupted

Unit operates in autonomous mode

Auto

CCN network fault

beween the two units for more than
2 mins.

68

Master/slave configuration error

Poor master/slave configuration

Master/slave control not allowed

Auto/manual in

Master/slave configuration

case of heating/

fault

cooling fault

69

Initial factory configuration necessary

All factory parameters are at zero

Unit prevented from starting

Auto

No factory configuration

70

Poor factory configuration.

Poor factory configuration

Ditto

Ditto

Factory configuration error

1. Compr. A3 configured and A2 absent
2. Compr. A4 configured and A2 or A3 absent
3. No lead compr. in circuit B
4. Compr. B3 configured and B2 absent
5. Compr. B4 configured and B2 or B3 absent
6. Difference of compressors in circ. A and B too high
7. Fan configured for a water-cooled condenser
8. No fans configured
9. Heat reclaim option configured, and heat reclaim
sensors not configured

71

CCN/Clock Board fault

The CCN/Clock Board is no longer

Unit shut down

No

Auto, if the board

CCN/Clock Board faulty

detected

is again detected

72

Emergency stop

An emergncy stop commend has been

Unit shut down

No

CCN

CCN network command

transmitted by the CCN network.

73

Pump No. 1 fault

Evaporator water pump operating

Unit shut down

No

Manual

Pump overheat or poor

contact open, when the pump has

pump connection

received a commmand to operate.

74

Pump No. 2 fault

Ditto

Unit shut down

No

Manual

Ditto

75

Condenser anti-freeze protection, circuit A

Saturated temperature is under the

Unit shut down. Condenser pump

No

Auto

Discharge pressure trans-

frost cut-out point

started, if unit is shut down

ducer faulty, refrigerant leak,
or low cond. water temp.

76

Condenser anti-freeze protection, circuit B

Ditto

Ditto

No

Auto

Ditto

77

Lack of water flow, condenser

Water flow switch (water-cooled units)

Unit shut down

No

Manual

Condenser pump, low water

not closed for 1 min.

flow, water flow switch

78

Condenser water flow fault, heat reclaim mode

Ditto

Units stays in cooling mode

No

Manual

Ditto

79

Heat reclaim mode fault, circuit A

More than two consecutive pumpdown

Circuit A stays in cooling mode

No

Manual

Leak or heat reclaim or drain

sequences not successful

solenoid shut-off valve fault

80

Heat reclaim mode fault, circuit B

Ditto

Circuit B stays in coolng mode

No

Manual

Ditto

81

High pressure fault, circuit A

Circuit operating and discharge pressure Unit shut down

No

Manual, the high

Fan circuit fault, air or

exceeds the high pressure cut-out point

pressure command condenser temperature too
must be reset

high

manually by the
button on the HP
pressure switch

82

High pressure fault, circuit B

Ditto

Ditto

No

Ditto

Ditto

83

Maintenance alert

A maintenance alert is active

None

Manual

1. Charge too low
2. Water loop too low
3. Air filter maintenance delay elapsed
4. Pump 1 maintenance delay elapsed
5. Pump 2 maintenance delay elapsed
6. Water filter maintenance delay elapsed