Crown Boiler CWD138 User Manual
Page 12

10
10
TABLE 3a: SUMMARY OF HORIZONTAL VENTING OPTIONS
VENT OPTION #
1
2
3
4
5
CLASSIFICATION USED IN THIS
MANUAL
HORIZONTAL
DIRECT VENT
HORIZONTAL
DIRECT VENT
(RESERVED
FOR FUTURE
USE)
HORIZONTAL
DIRECT
EXHAUST
HORIZONTAL
DIRECT
EXHAUST
ILLUSTRATED IN FIGURE
8a OR 8b
8a OR 8b
9
9
VENT PIPE STRUCTURE
PENETRATION
WALL
WALL
WALL
WALL
AIR INTAKE PIPE STRUCTURE
PENETRATION
WALL
WALL
N.A.
N.A.
VENT PIPE SIZE
3”
4”
3”
4”
AIR INTAKE PIPE SIZE
4”
4”
N.A.
N.A.
MAXIMUM VENT
PIPE LENGTH
CWD060 - CWD138
55 FT
55 FT
55 FT
55 FT
CWD165
35 FT
55 FT
35 FT
55 FT
CWD193
25 FT
55 FT
25 FT
55 FT
CWD220
15 FT
55 FT
15 FT
55 FT
CWD245
N.R.
55FT
10 FT
55 FT
MAXIMUM
INT
AKE PIPE
LENGTH
CWD060 - CWD138
60 FT
60 FT
N.A.
N.A.
CWD165
40 FT
60 FT
N.A.
N.A.
CWD193
30 FT
60 FT
N.A.
N.A.
CWD220
20 FT
60 FT
N.A.
N.A.
CWD245
N.R.
60 FT
N.A.
N.A.
EXHAUST TERMINAL
3” 90 ELBOW,
TEE, OR
CROWN
COAXIAL
TERMINAL
#50-003
4” 90 ELBOW,
TEE, OR
CROWN
COAXIAL
TERMINAL
#50-004
3” 90 ELBOW
OR TEE
4” 90 ELBOW
OR TEE
AIR INTAKE TERMINAL
4” 90 ELBOW
OR CROWN
COAXIAL
TERMINAL
#50-003
4” 90 ELBOW
OR CROWN
COAXIAL
TERMINAL
#50-004
N.A.
N.A.
VENT MATERIAL
APPROVED VENT SYSTEM SHOWN IN TABLE 4
AIR INTAKE MATERIAL
GALVANIZED OR PVC
N.A.
N.A.
“N.R” - Not recommended “N.A.” - Not applicable