TABLE 3a: SUMMARY OF HORIZONTAL VENTING OPTIONS

VENT OPTION #

1

2

3

4

5

CLASSIFICATION USED IN THIS
MANUAL

HORIZONTAL

DIRECT VENT

HORIZONTAL

DIRECT VENT

(RESERVED

FOR FUTURE

USE)

HORIZONTAL

DIRECT

EXHAUST

HORIZONTAL

DIRECT

EXHAUST

ILLUSTRATED IN FIGURE

8a OR 8b

8a OR 8b

9

9

VENT PIPE STRUCTURE
PENETRATION

WALL

WALL

WALL

WALL

AIR INTAKE PIPE STRUCTURE
PENETRATION

WALL

WALL

N.A.

N.A.

VENT PIPE SIZE

3”

4”

3”

4”

AIR INTAKE PIPE SIZE

4”

4”

N.A.

N.A.

MAXIMUM VENT

PIPE LENGTH

CWD060 - CWD138

55 FT

55 FT

55 FT

55 FT

CWD165

35 FT

55 FT

35 FT

55 FT

CWD193

25 FT

55 FT

25 FT

55 FT

CWD220

15 FT

55 FT

15 FT

55 FT

CWD245

N.R.

55FT

10 FT

55 FT

MAXIMUM

INT

AKE PIPE

LENGTH

CWD060 - CWD138

60 FT

60 FT

N.A.

N.A.

CWD165

40 FT

60 FT

N.A.

N.A.

CWD193

30 FT

60 FT

N.A.

N.A.

CWD220

20 FT

60 FT

N.A.

N.A.

CWD245

N.R.

60 FT

N.A.

N.A.

EXHAUST TERMINAL

3” 90 ELBOW,

TEE, OR
CROWN

COAXIAL

TERMINAL

#50-003

4” 90 ELBOW,

TEE, OR
CROWN

COAXIAL

TERMINAL

#50-004

3” 90 ELBOW

OR TEE

4” 90 ELBOW

OR TEE

AIR INTAKE TERMINAL

4” 90 ELBOW

OR CROWN

COAXIAL

TERMINAL

#50-003

4” 90 ELBOW

OR CROWN

COAXIAL

TERMINAL

#50-004

N.A.

N.A.

VENT MATERIAL

APPROVED VENT SYSTEM SHOWN IN TABLE 4

AIR INTAKE MATERIAL

GALVANIZED OR PVC

N.A.

N.A.

“N.R” - Not recommended “N.A.” - Not applicable