Crown Boiler CWD138 User Manual
Page 61
                                    Advertising
                                    
                                        
                                    
                                
                                 
59
59
N
Y
Y
Call for heat
from
"DHW/H2"
zone
"DHW/H2"
circulator
start?
Defective
CB502 board
DHW
LED On?
24V across
"DHW/H2" T
and T
* Loose connection in 
t'stat or zone valve end 
switch wiring
* Defective t'stat or zone 
valve end switch
* T'stat or zone system 
miswired-consult zone 
valve or t'stat 
manufacturer's 
instructions.
N
120 volts across
blue and white
circulator leads?
*Loose 
connection 
between boiler 
J-box and circ 
* Defective "DHW/H2" 
relay on CB502 
* Relay not fully seated 
in socket
* Loose connection in 
circulator wiring
Y
N
N
Continued on
next page
Y
TROUBLESHOOTING CHART FOR BOILERS WITH CB502 CONTROL SYSTEM (USING #42-502A BOARD)
PAGE 2 OF 4
                                    Advertising