TABLE 3c : SUMMARY OF VERTICAL COAXIAL VENTING OPTIONS

VENT OPTION #

11

12

13

CLASSIFICATION USED IN THIS
MANUAL

VERTICAL

COAXIAL

DIRECT VENT

VERTICAL

COAXIAL

DIRECT VENT

VERTICAL

COAXIAL

DIRECT VENT

VENT PIPE STRUCTURE
PENETRATION

ROOF

ROOF

ROOF

AIR INTAKE PIPE STRUCTURE
PENETRATION

ROOF

ROOF

ROOF

VENT PIPE SIZE

3”

3”

4”

AIR INTAKE PIPE SIZE
(NON-COAXIAL SECTION)

4”

4”

4”

AIR INTAKE PIPE SIZE

(COAXIAL SECTION)

5”

5”

7”

MAXIMUM VENT

PIPE LENGTH

CWD060 - CWD138

47 FT

47 FT

47 FT

CWD165

27 FT

27 FT

CONSULT

FACTORY

CWD193

N.R.

N.R.

CWD220

N.R.

N.R.

CWD245

N.R.

N.R.

MAXIMUM LENGTH
COAXIAL SECTION

30 FT OR AS

LIMITED BY MAX

VENT LENGTH,
WHICHEVER IS

LESS

AS LIMITED

BY MAX VENT

LENGTH

CONSULT
FACTORY

MAXIMUM

INT

AKE PIPE

LENGTH

CWD060 - CWD138

52 FT

50 FT

50 FT

CWD165

32 FT

32 FT

CONSULT

FACTORY

CWD193

N.R.

N.R.

CWD220

N.R.

N.R.

CWD245

N.R.

N.R.

EXHAUST TERMINAL

BY VENT

SYSTEM

MANUFAC-

TURER. SAME

DIAMETER AS

VENT SYSTEM.

SEE TABLE 4.

HEAT FAB

#SC03RC

HEAT FAB

#SC04RC

AIR INTAKE TERMINAL

SUPPLIED WITH
CROWN #500005

COAXIAL VENT

KIT

HEAT FAB

#SC03VT

HEAT FAB

#SC04VT

ADAPTOR FROM NON-COAXIAL
TO COAXIAL SECTIONS

5” “B” VENT

TEE + SUPPORT

SUPPLIED WITH
CROWN #500005

COAXIAL VENT

KIT

HEAT FAB

#SC03TAD4

HEAT FAB

#SC04TAD4

VENT MATERIAL
(NON-COAXIAL SECTION)

APPROVED

VENT SYSTEM

SHOWN IN

TABLE 4

HEAT FAB

SAF-T VENT

HEAT FAB

SAF-T VENT

VENT MATERIAL
(COAXIAL SECTION)

APPROVED

VENT SYSTEM

SHOWN IN

TABLE 4

HEAT FAB

SAF-T VENT SC

HEAT FAB

SAF-T VENT SC

AIR INTAKE MATERIAL
(NON-COAXIAL SECTION)

GALVANIZED OR PVC

AIR INTAKE MATERIAL
(COAXIAL SECTION)

5” TYPE “B”

VENT

HEAT FAB

SAF-T VENT SC

HEAT FAB

SAF-T VENT SC

“N.R” - Not recommended “N.A.” - Not applicable