Dell PowerEdge Rack Enclosure 4620S User Manual

Page 13

Advertising
background image

Dell Inc. | Data Center Infrastructure

13

Figure 12: Zero U Mount PDUs



In order to install Zero U mount PDUs with hardwired cables and connectors that are too large to fit through the gap
between the rear mounting rail and the PDU trays, follow these steps for mounting:

1. Insert the PDU through the gap between the rear mounting rail and the PDU tray. Installation should be

from the inside of the rack.

2. From the side of the rack, snap the PDU tray into the mounting rail. Ensure that the cable is tucked back

into the rack so that there’s no interference between either a side panel or with any part of an adjacent rack.
See Figure 13.

3. Once PDUs are installed, connect equipment power cords and dress them to assure that they are not under

stress.





















Advertising
This manual is related to the following products: