Dell UPS 1920R User Manual

Page 48

Advertising
background image

48

|

Operation

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Battery Saving Mode

[Disabled] [10%] [20%] [30%]...[100%]

The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.

Disabled

On Battery Notice Delay

[0] [1s] [2s]...[99s]

The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.

0s

Site Wiring Fault Alarm

[Enabled] [Disabled]

Disabled for 208V
models; Enabled for
all others

External Battery Module (EBM)

[0] [1]

See “Configuring the UPS for an EBM” on page 54.

0

Charger

[Enabled] [Disabled]

If Enabled, batteries charge normally.

If Disabled, the battery charger is off.

Enabled

Battery Charge % to Restart

[0%] [10%] [20%] [30%]...[100%]

When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0, the feature is disabled.

0%

Battery Low Alarm

[Immediate] [2 min] [3 min] [5 min]

If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.

3 min

Automatic Battery Tests

[Enabled] [Disabled]

See “Running Automatic Battery Tests” on page 55.

Enabled

Advertising