Dell UPS 1920R User Manual

Page 68

Advertising
background image

68

|

Specifications

Table 15. Battery

Configuration

1000W: (3) 12V, 9 Ah internal batteries (no EBM)

1920/1500W: (6) 12V, 9 Ah internal batteries; (12) 12V, 9 Ah EBM

2700/2300W: (8) 12V, 9 Ah internal batteries; (16) 12V, 9 Ah EBM

Voltage

1000W: 36 Vdc internal (no EBM)

1920/1500W: 72 Vdc internal; 72 Vdc EBM

2700/2300W: 96 Vdc internal; 96 Vdc EBM

Fuses

Internal batteries: (2) 30A fuses

EBM: (4) 30A fuses

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

Charging

Approximately 4 hours to 90% usable capacity at nominal line and no

supplementary power supply load

Monitoring

Advanced monitoring for earlier failure detection and warning

Battery Runtimes*

Internal batteries: 5 minutes at full load/14 minutes at half load

1920/1500W with one EBM: 19 minutes at full load/46 minutes at half load

2700/2300W with one EBM: 19 minutes at full load/45 minutes at half load

*Battery runtimes are approximate and vary depending on the load configuration and battery charge.

DC/DC

Converter

Input
Filter

AVR

Output

Filter

Charger

Battery

DC/AC

Inverter

Figure 38. Line-Interactive UPS Block Diagram