PRE-START-UP

IMPORTANT: Before beginning Start-Up, complete
Start-Up Checklist on pages CL-1 to CL-4. This check-
list assures proper start-up of a unit, and provides a
record of unit condition, application requirements, sys-
tem information, and operation at initial start-up.

ELECTRIC SHOCK HAZARD
Open all disconnects before servicing this
equipment. There may be more than one
disconnect.

Initial Check

IMPORTANT: Electrical power source must agree
with unit nameplate rating. Do not start the chiller, even
momentarily, until the following checks have been
completed.

1. Check all auxiliary components, such as cooling tower

(if used), chilled liquid and condenser water pumps, air-
handling equipment, or other equipment to which
the chiller supplies liquid. Consult manufacturer’s
instructions.

2. Be sure flow switch is properly installed and set. See

instructions packaged with flow switch accessory.

3. Set the temperature controller deadband as specified in

Tables 5 and 6. Set point should be at the desired cooler
leaving fluid temperature. Refer to Chilled Fluid Tem-
perature Controller section on page 29 for additional dead-
band setting information.

4. Backseat (open) compressor suction and discharge shut-

off valves. Crack open valves (one turn in) to allow some
pressure to each test gage (if installed).

5. Backseat (open) liquid line shutoff valve(s).
6. Open valve to capillaries from fluid regulating valve (when

used).

7. Fill chilled fluid liquid circuit with clean water or other

noncorrosive fluid to be cooled. Bleed all air out of the
high points of the system. Set flow rate according to job
requirements. See Table 3. If the chilled water is to be
maintained at a temperature below 40 F (4.4 C), a brine
of sufficient concentration must be used to prevent freeze-up
at anticipated suction temperatures.

8. Open supply valve (or fill cooling tower, if used) for

condenser water.

9. Check tightness of all electrical connections.

LEGEND

C

Contactor

CB

Circuit Breaker

CM

Control Module

COM — Common
CR

Control Relay

SW

Switch

TB

Terminal Block

TDR

Time Delay Relay

THERM — Termistor
TRAN

Transformer

GCS

Ground Current Sensor

GND

Ground

NC

Normally Closed

NEUT — Neutral
NO

Normally Open

Fig. 20 — 30HW Control Box Components Label