START-UP CHECKLIST FOR CHILLER SYSTEMS

(Remove and use for job file)

A. Preliminary Information

JOB NAME

LOCATION

INSTALLING CONTRACTOR

DISTRIBUTOR

START-UP PERFORMED BY

EQUIPMENT:

Chiller:

MODEL #

SERIAL #

COMPRESSORS:

CIRCUIT #1

CIRCUIT #2 (30HK,HL ONLY)

MODEL #

MODEL #

SERIAL #

SERIAL #

MOTOR #

MOTOR #

CONDENSER (30HK, HWB, HWC, HWS ONLY):

MODEL #

SERIAL #

COOLER:

MODEL #

MANUFACTURED BY

SERIAL #

DATE

AIR-HANDLING EQUIPMENT:

MANUFACTURER

MODEL #

SERIAL #

ADDITIONAL AIR-HANDLING UNITS AND ACCESSORIES

B. Preliminary Equipment Check

(YES or NO)

IS THERE ANY SHIPPING DAMAGE?

IF SO, WHERE

WILL THIS DAMAGE PREVENT UNIT START-UP?

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(refer to Installation Instructions)

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(refer to Installation Instructions)

HAS THE GROUND WIRE BEEN CONNECTED?

ARE ALL TERMINALS TIGHT?

ON 30HW UNITS, IS THE THERMISTOR SECURELY STRAPPED TO THE COOLER LEAVING CHILLED FLUID LINE, AND
IS IT PROPERLY INSULATED?

ON 30HW UNITS, IS YELLOW WIRE GOING TO TRANSFORMER 1 (POWER TRANSFORMER) ON THE CORRECT
TERMINAL (TERMINAL H2 FOR 208 V AND 575 V; TERMINAL H3 FOR 230 V, 380 V, AND 400 V, TERMINAL H4
FOR 460 V)?

IF UNIT IS A MEDIUM TEMPERATURE BRINE UNIT, IS TEMPERATURE CONTROLLER SET FOR BRINE AND NOT
FOR WATER? IF UNIT IS NOT A BRINE UNIT, IS TEMPERATURE CONTROLLER SET FOR WATER AND NOT FOR
BRINE?

HAVE TEMPERATURE CONTROLLER, CONTROL MODULE AND CONTROL RELAY CONNECTIONS BEEN CHECKED
FOR TIGHTNESS?

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 2
Tab

5c

PC 903

Catalog No. 533-070

Printed in U.S.A.

Form 30H-10SI

Pg CL-1

11-98

Replaces: 30H-8SI