Table 14 — Troubleshooting (cont)

SYMPTOMS

CAUSE

REMEDY

Compressor
loses oil

Leak in system

Repair leak.

Mechanical damage (blown piston or broken
discharge valve)

Repair damage or replace compressor as needed.

Oil trapped in line

Check piping for oil traps.

Crankcase heater not energized
during shutdown

Check wiring and crankcase heater contacts on the
temperature controller, and replace heater if necessary.

Hot liquid line

Shortage of refrigerant due to leak

Repair leak and recharge.

Frosted liquid line

Shutoff valve partially closed or restricted

Open valve or remove restriction.

Restricted filter drier

Replace filter drier.

Frosted suction line

Expansion valve admitting excess refrigerant

Adjust expansion valve. Replace valve if defective.

Compressor will
not unload

Burned-out coil

Replace coil.

Defective capacity control valve

Replace valve.

Miswired solenoid

Rewire correctly.

Weak, broken, or wrong valve body spring

Replace spring.

Compressor will
not load

Miswired solenoid

Rewire correctly.

Defective capacity control valve

Replace valve.

Plugged strainer (high side)

Clean or replace strainer.

Stuck or damaged unloader piston or piston ring(s)

Clean or replace the necessary parts.

System noises

Piping vibration

Support piping as required.
Check for loose pipe connectors.

Expansion valve hissing

Add refrigerant.
Check for plugged liquid line strainer.

Compressor noisy

Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.

Freeze-up

Improper charging

Make sure a full quantity of fluid is flowing through the
cooler while charging, and suction pressure in cooler is
equal to or greater than pressure corresponding to 32 F
(0° C) (58 psig [400 kPa] for Refrigerant 22).

Improperly set safety thermostat

Check safety thermostat for proper setting at beginning of
each season.

Operating with safety thermostat bypassed

If thermostat was bypassed for checking, be sure it is back
in circuit before starting unit.

Improper circulation of condenser water

Use adequately sized cleanable strainer in the condenser
water circuit. Make sure strainer is clean. It may sometimes
be necessary to chemically treat the water to prevent for-
mation of deposits.

System not drained for winter shutdown

Remove drain plugs at end of cooling season. Blow out any
residual water. Instead of draining, a suitable anti-freeze
may be added to the water.

Damage to chiller due to freez-

ing is considered abuse and is not covered by warranty.

Loose Thermistor

Tighten thermistor to pipe and reinsulate (30HW).