COOLING LOAD SATISFIED — Unit shuts down if cool-
ing load is satisfied. Unit restarts if required after comple-
tion of 5-minute timer cycle.

THERMISTOR FAILURE — If thermistor fails in open mode,
the temperature controller shuts down the unit in an out-of-
range condition. Replace the thermistor. Unit restarts auto-
matically after completion of a 5-minute timer cycle, and
when the leaving cooler chilled fluid temperature rises above
the upper deadband limit of the temperature controller.

NOTE: If the thermistor fails in closed mode, the tempera-
ture controller keeps trying to load up.

If unit stoppage occurs more than once as a result of
any of the safety devices listed, determine and correct
cause before attempting another restart.

Table 14 — Troubleshooting

SYMPTOMS

CAUSE

REMEDY

Compressor does
not run

Power line open

Reset circuit breaker.

Control fuse or circuit breaker opens

Check control circuit for ground or short. Reset breaker
and replace fuse.

Compressor overtemperature sensor open

Find cause of high temperature and reset controls.

Tripped power breaker

Check the controls. Find the cause of trip and
reset breaker.

Condenser circulating pump not running

Power off — restart.
Pump binding — free pump.
Incorrect wiring — rewire.
Pump motor burned out — replace.

Loose terminal connection

Check connections.

Improperly wired controls

Check wiring and rewire if necessary.

Low line voltage

Check line voltage — determine location of voltage drop
and remedy deficiency.

Compressor motor defective

Check motor winding for open or short. Replace
compressor if necessary.

Seized compressor

Replace compressor.

Compressor cycles
off on loss of
charge

Loss of charge control erratic in action

Repair leak and recharge.
Replace control.

Low refrigerant charge

Add refrigerant.

Low suction temperature

Raise cooler leaving fluid temperature set point.

Compressor suction valve leaking

Replace valve plate.

Plugged compressor suction strainer

Clean or replace strainer.

Compressor suction shutoff valve partially closed

Open valve.

Compressor cycles
off on out of range
condition

Thermistor failure

Replace thermistor.

System load was reduced faster than
controller could remove stages

Unit will restart after fluid temperature rises back into the
control band. Avoid rapidly removing system load.

Compressor cycles control
steps rapidly

Temperature controller deadband setting is
too low

Raise deadband setting.

Compressor shuts
down on high-
pressure control

High-pressure control acting erratically

Replace control.

Compressor discharge valve partially closed

Open valve or replace (if defective).

Air in system

Purge system.

Condenser scaled/dirty

Clean condenser.

Receiver not properly vented — refrigerant
backs up into evaporator condenser

Repipe as required to provide adequate venting.

Condenser water pump or fans not operating

Start pump — repair or replace if defective.

System overcharged with refrigerant

Reduce charge.

Unit operates too long
or continuously

Low refrigerant charge

Add refrigerant.

Control contacts fused

Replace control.

Air in system

Purge system.

Partially plugged or plugged expansion valve
or filter drier

Clean or replace as needed.

Defective insulation

Replace or repair as needed.

Service load

Keep doors and windows closed.

Inefficient compressor

Check valves, and replace if necessary.

Unusual or loud system
noises

Piping vibration

Support piping as required.
Check for loose pipe connections.

Expansion valve hissing

Add refrigerant.
Check for plugged liquid line filter drier.

Compressor noisy

Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.

38