SETTING GATE CONTROL SWITCH S1 AND RECLOSE TIMER POT R94

NOTE: For complete details on controls, indicators adjustments and inputs, see Appendix A.

1. GATE CONTROL SWITCH (S1)

Figure 10. Gate Control Switch S1 Location.

SLIDE ACTION

When used with ATG, this switch controls several gate operator features:

(S1-1)

Inside Interrupt Loop: four different modes are selectable:

SLIDE and ATG OFF:

Loop activation prevents the gate from opening or closing. If

gate is moving, Loop activation stops the gate. When the Loop clears, the gate

resumes its course.

SLIDE only ON:

Loop activation prevents the gate from closing. If gate is closing, Loop

activation opens the gate and starts the Reclose Timer, if timer is on.

ATG only ON:

Loop activation prevents the gate from opening or closing. If gate is

closing, a Loop activation stops the gate. When the Loop clears, the gate resumes

closing. If the gate is opening or fully open, as soon as the Loop clears, the gate

immediately begins closing to discourage tailgaters.

SLIDE and ATG ON:

Loop activation prevents the gate from closing. When the Loop

clears, the gate resumes closing. If gate is opening or fully open, as soon as the

Loop clears, the gate immediately begins closing to discourage tailgaters.

Dynamic Braking: When SLIDE is ON, gate brakes whenever it stops.

When SLIDE is OFF, gate brakes only at open or close limit.

TIMER

Sets the Reclose Timer to OFF (left) or ON (right). When enabled, the timer controls

(S1-2)

how long the gate waits at the open limit before closing. The Reclose Timer can be

set from 0-250 seconds by adjusting the Reclose Timer pot (R94). During a power

outage, if the gate is fully open and TIMER is ON, the Reclose Timer starts after the

restoration of power, causing the fully open gate to close automatically.

RETRY

Sets the Retry function to OFF (left) or ON (right). When enabled, if the gate meets

(S1-3)

an obstacle, a closing gate reverses and an opening gate stops, waits 30 seconds,

then tries to resume. The gate will re-try twice before it faults out.

ATG

Sets Anti-Tailgate function to OFF (left) or ON (right). The Anti-Tailgate feature helps

(S1-4)

prevent two cars from entering on one OPEN command.

MASTER

In conjunction with the TRAP switch, sets configuration for master/slave system.

(S1-5)

TRAP

In conjunction with the MASTER switch, sets configuration for master/slave system.

(S1-6)