Adjustments – Chamberlain Swing GATE User Manual

Page 48

Advertising
background image

Rev C

Doc 6001242 (01-20273)

47 of 53

INS./OUTS. INT. SENSE / SHADOW SENSE / EXIT SENSE (TB12/TB13/TB14/TB15) INPUTS

INSIDE

Input from an Inside Interrupt loop provides the signal for an optional

LiftMaster INTERRUPT

loop detector add-on board. Operation is the same as the

Interrupt Loop SENSE

input, above.

OUTSIDE

Input from an Outside Interrupt loop provides the signal for an optional

INTERRUPT

LiftMaster loop detector add-on board. Operation is the same as the

Interrupt SENSE Loop input, above.
SHADOW

Input from shadow loop provides signal for optional LiftMaster loop detector

SENSE

add-on board. Operation is the same as Shadow Loop input, above.

EXIT

Input from exit loop provides signal for optional LiftMaster loop detector add-

on SENSE

board. Operation is the same as Exit Loop input, above.

RADIO INPUT (TB6)

RADIO RECV

Convenience terminals provide power (24VAC, 200mA) and signal
connection for a radio receiver. Activation is the same as CYCLE.

MAG LOCK INPUT (TB4)

MAG LOCK

NO and COM inputs can close a circuit (i.e., MagLock) when the Close Limit
switch is activated (the gate is fully closed).
NC and COM inputs close a circuit (security camera, camcorder, light, etc.)
when the Close Limit switch is deactivated (when gate is not fully closed).

SLAVE I/O INPUT (TB1)

SLAVE I/O

Input/output terminals are used to control a second gate operator in a
Master/Slave system.

ADJUSTMENTS

OVERLOAD

Factory-set pot protects the gate operator from excessive motor current.

(R71)

If RETRY is ON, when the limit is exceeded, a closing gate reverses a few

inches and stops, and an opening gate stops, waits 30 second, then tries to

resume. The gate will retry twice before faulting out.

NOTE: Gate may be more sensitive to drag in one direction than the other.

NOTE: For swing gate operation, controls are Right/Clockwise and Left/Counterclockwise.

REVERSE

Adjustable pot controls gate sensitivity to blockages by the instantaneous

RIGHT (R78)

rise in motor current. If RETRY is ON, when the limit is exceeded, a closing

gate opens fully and an opening gate stops, waits 30 seconds, then tries to

resume. The gate will retry twice before faulting out.

REVERSE

Adjustable pot controls gate sensitivity to blockages by the instantaneous

LEFT (R81)

rise in motor current. If RETRY is ON, when the limit is exceeded, a closing

gate opens fully and an opening gate stops, waits 30 seconds, then tries to

resume. The gate will retry twice before faulting out.

NOTE: LiftMaster gate operators have two reverse sense adjustments (left and right)

where other gate operators have only one. This allows greater flexibility of
installation. For instance, you can install a gate on an incline and not worry
about sacrificing downhill gate sensitivity.

INRUSH

Adjustable pot controls the delay in sensitivity to a reverse sense input.

(R119)

This delay in sensitivity prevents the initial motor inrush current from

causing a fault condition. The weight of the gate determines this setting.

RECLOSE

Adjustable pot controls the time delay between gate reaching full open and

TIMER (R94)

starting to reclose. The Reclose Timer is adjustable from 0-250 seconds.

Advertising