Electrical option, Requires detex power supply – Detex Delayed Egress With Magnetic Lock User Manual

Page 3

Advertising
background image

Detex requires one fire alarm

relay per power supply

Closed Fire Alarm Loop

(must be supplied for power

output)

FACTORY INSTALLED

JUMPER

RED

BLK

Fire Loop

Sense

To Exit Device

Door #1

REQUIRED WIRE SIZES:

STRANDED WIRE GAUGE: 18 AWG MIN

MAXIMUM LENGTH OF TWO CONDUCTOR CABLE: 40 FEET

DETEX REQUIRES THE POWER

SUPPLY BE LOCATED WITHIN

40 FEET OF THE DEVICE

WHITE

BLACK

GREEN

RED

BLACK

RED

BLACK

To Exit Device

Door #2 (if req'd)

RED/BLK WIRES

TO 24 VOLT

Orange and Blue wires to MAGNET

DO NOT ADD POWER!

(PC BOARD ASSEMBLY INSIDE

DELAYED EGRESS DEVICE)

To disable the low-battery

indication, slide the Dis Lo Bat

switch to 'ON'

RED

BLK

From (-) terminal

to pin #2 on exit

device

From (+) terminal

to pin #1 on exit

device

9V Alkaline

Battery

90-800 Power Supply with Detex Delayed Egress device

REQUIRES DETEX POWER SUPPLY

ELECTRICAL OPTION

104878 Page 3