Hardwire transfer options, Riser diagram – Detex Delayed Egress With Magnetic Lock User Manual

Page 5

Advertising
background image

REFER TO WIRING &

FIRE ALARM DIAGRAMS

FOR WIRING

INSTRUCTIONS

DETEX DELAYED EGRESS

PANIC HARDWARE

INSTALLED BY

TRAINED TECHNICIAN

DOOR SIGN SUPPLIED WITH

DETEX DELAYED EGRESS

PANIC HARDWARE

PROVIDE WIRING CONDUIT, CONNECTOR,

ETC BETWEEN DETEX POWER SUPPLY AND

FIRE ALARM CONTROL PANEL AS REQUIRED

TO ALLOW THE FIRE ALARM SYSTEM TO

OVERRIDE THE DETEX DELAYED EGRESS

FEATURE DURING A FIRE ALARM

THE LOSS OF POWER OR OPEN FIRE

ALARM CIRCUIT WILL ELIMINATE THE

DELAY EGRESS OPERATIONS

Electric Hinge

p/n: EWH8-X

Power Transfer

Electric Hinge Endcap Prep

Power Transfer Endcap Prep

FCA Flex Conduit Endcap Prep

HARDWIRE TRANSFER OPTIONS

1/2" Hole through the

inside door face

Wire chase through door

1/2" Hole through the

inside door face

Wire chase through door

Flex Conduit/End Cap Kit

p/n: FCA

(Order FCA x Finish)

p/n: PT-5

Note: For high traffic areas an electric through-wire hinge or power transfer is recommended.

J

DETEX FILTERED AND REGULATED POWER

SUPPLY WITH FIRE ALARM SYSTEM LOOP

24 VDC @1 AMP min.

DETEX REQUIRES THE POWER SUPPLY BE LOCATED

WITHIN 40 FEET OF THE DEVICE

DETEX MAG LOCK

SUPPLIED WITH

DETEX DELAYED

EGRESS PANIC

HARDWARE

J

REQUIREMENTS:

MIN. 22 GA STRANDED WIRE FOR SIGNALING

MIN. 18 GA STRANDED WIRE FOR POWER

RISER DIAGRAM

104878 Page 5