Ee electrical option, Requires detex power supply – Detex V40 EE User Manual

Page 9

Advertising
background image

REQUIRES DETEX POWER SUPPLY

REQUIRED WIRE SIZES:

STRANDED WIRE GAUGE: 18 AWG MIN

MAXIMUM LENGTH OF TWO CONDUCTOR CABLE: 40 FEET

Detex requires one fire

alarm relay per power

supply

Closed Fire Alarm Loop

(must be supplied)

Door #2

(if req'd)

To Exit Device

RED/BLK WIRES

TO 24 VOLT

Red wires to internal solenoid

DO NOT ADD POWER!

(PC BOARD ASSEMBLY INSIDE

DELAYED EGRESS DEVICE)

To disable the low-battery

indication, slide the Dis Lo Bat

switch to 'ON'

RED

BLK

From (-) terminal

to pin #2 on exit

device

From (+) terminal

to pin #1 on exit

device

9V Alkaline

Battery

FACTORY INSTALLED

JUMPER

RED

BLK

Fire Loop

Sense

To Exit Device

Door #1

DETEX REQUIRES THE POWER

SUPPLY BE LOCATED WITHIN

40 FEET OF THE DEVICE

WHITE

BLACK

GREEN

RED

BLACK

RED

BLACK

EE ELECTRICAL OPTION

Power Supply with Detex Delayed Egress device

103185 Page 9