Ee electrical option, Requires detex power supply – Detex V40 EE User Manual
Page 9
REQUIRES DETEX POWER SUPPLY
REQUIRED WIRE SIZES:
STRANDED WIRE GAUGE: 18 AWG MIN
MAXIMUM LENGTH OF TWO CONDUCTOR CABLE: 40 FEET
Detex requires one fire
alarm relay per power
supply
Closed Fire Alarm Loop
(must be supplied)
Door #2
(if req'd)
To Exit Device
RED/BLK WIRES
TO 24 VOLT
Red wires to internal solenoid
DO NOT ADD POWER!
(PC BOARD ASSEMBLY INSIDE
DELAYED EGRESS DEVICE)
To disable the low-battery
indication, slide the Dis Lo Bat
switch to 'ON'
RED
BLK
From (-) terminal
to pin #2 on exit
device
From (+) terminal
to pin #1 on exit
device
9V Alkaline
Battery
FACTORY INSTALLED
JUMPER
RED
BLK
Fire Loop
Sense
To Exit Device
Door #1
DETEX REQUIRES THE POWER
SUPPLY BE LOCATED WITHIN
40 FEET OF THE DEVICE
WHITE
BLACK
GREEN
RED
BLACK
RED
BLACK
EE ELECTRICAL OPTION
Power Supply with Detex Delayed Egress device