Detex ML-1549W User Manual

Page 2

Advertising
background image

WIRING DETAILS:

To Properly

Fused DC Power

source

(-)

(+)

BLU

BLK

BRN

RED

(+)

(-)

24VDC @225mA

24VDC CONFIGURATION

4. Mount the ElectroMagnetic Lock with hardware provided (See pages 3).

5. Tighten all screws. Install anti-tamper plugs over socket head mounting screws .

6. Install 1/2” or 3/4” conduit. A conduit outlet box must be provided within 15" of the lock for wire connections.

7. Make all wire connections to a fused power source with the power off .

INSTALLATION (CONT.):

150

18

18

18

16

16

14

14

12

AMPS

0.25

0.50

0.75

1.00

1.50

2.00

2.50

3.00

3.50

25

18

18

18

18

18

18

18

18

18

50

18

18

18

18

18

18

18

16

16

75

18

18

18

18

18

18

16

14

14

100

18

18

18

18

16

16

14

14

12

200

18

18

16

16

14

14

12

12

250

18

18

16

14

12

12

300

18

16

16

14

400

18

16

14

12

500

16

14

12

1000

16

DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE

To determine the correct wire gauge to use on a single “circuit” the following information is required :

1. The quantity, voltage and current draw of all lock (s) to be connected to the circuit.

2. The distance in feet from the power supply to the furthest lock on the circuit .

Add together the current draw (amps) of all locks on the same circuit. Using the AWG Chart below, cross reference the

total amps with the distance between the power source and the furthest lock to determine the wire gauge required .

A single “circuit” describes a pair of wires run from the power supply to one or more locks that are wired in parallel . The

distance from the power supply to the furthest lock in the “circuit” must not exceed the distance number shown in the

chart below and is based on your selected wire gauge . If the distance shown in the chart is inadequate for your

application , divide your locks up into 2 or more separate “circuits” and use the chart to check each circuit independently .

Fewer locks on each circuit may allow you to use a smaller gauge wire or will allow you to increase the maximum

distance between the power supply and the furthest lock on the circuit . More than one circuit can be connected on the

same power supply as long as the combined current required from all connected circuits does not exceed the power

supply rating .

NOTE: All wiring must be installed in accordance with all state and local codes .

Page 2

103163

ML-1500

ELECTROMAGNETIC

LOCK

Minimum Wire Gauge

For 24 Volts DC

Grn, Yell, Org wires not used