TROUBLE SHOOTING

ML-1549W / ML-1549WF ELECTROMAGNETIC LOCK

Page 4

103163

PROBLEM

CAUSE

SOLUTION

Poor holding power

Armature installed rigidly .

Insufficient voltage

The armature must pivot loosely form its center

mounting point to permit full armature contact

Check for proper voltage at the ElectroMagnetic lock input . If

the voltage is low, determine if the correct wire gauge is being

used to prevent excessive voltage drop .

No magnetic power.

Door does not lock.

No power

Check the input voltage at the ElectroMagnetic lock . If the voltage

is zero or a low reading , double check all wire connections

Input polarity reversed .

Note polarity: 24VDC

RED = positive

BRN = negative

Blue and black wires spliced together

Open circuit in lock coil.

Check the ElectroMagnetic lock coil continuity with OHM

meter. If reading is high or open , replace the magnet

Coil short.

A coil short or incorrect wiring will blow fuses. Measure the coil for

correct resistance . If the coil reading is zero or low , replace the

magnet .

If the coil resistance is correct, check the field wiring for

shorts. Locate and repair the short in the field wiring .