Tightening torque

6.35(1/4")

9.52(3/8")

12.7(1/2")

15.88(5/8")

19.05(3/4")

Table 1

Torque based upon the wrench to be used

Strengthened tightening torque

160kgf.cm(63kgf.inch)

300kgf.cm(118kgf.inch)

500kgf.cm(197kgf.inch)

750kgf.cm(295kgf.inch)

1200kgf.cm(472kgf.inch)

200kgf.cm(79kgf.inch)

350kgf.cm(138kgf.inch)

550kgf.cm(216kgf.inch)

800kgf.cm(315kgf.inch)

1400kgf.cm(551kgf.inch)

*

Pipelines connection

*

*

Ordinary pipelines connection

(it is suitable for non-quick coupler)

No dust ,foreign articles,air or moisture should be allowed to enter the air conditioning system.Careful

attention should be paid when pipeline connection for outdoor unit is made.Try to avoid repeated

curves as much as possible,otherwise hardening or cracks might be caused to the copper pipes.Suitable

wrenches should be used when the pipeline connection is done so as to ensure appropriate torque(refer

to following torque Table 1).Excessive torque might damage the joints while too little torque might

lead to leakage.

INSTALLATION & REPAIR GUIDE

Split Wall-Mounted Air Conditioner

7