Tjernlund DCOP1 Constant Operating Pressure Draft Control 8504174 (Discontinued) User Manual

Page 11

Advertising
background image

10

UC1 UNIVERSAL CONTROL AND WHKE INTERLOCK KIT

CONNECTED WITH A MILLIVOLT APPLIANCE

SWITCH ARE INCLUDED WITH WHKE KIT.

950-0470 JUNCTION ADAPTER AND GAS PRESSURE

950-0470 (JA1) THERMOCOUPLE JUNCTION ADAPTER.

LINEAR LIMIT SPILL SWITCH IN SERIES WITH HIGH LIMIT

ON 750 MILLIVOLT (POWER PILE) WATER HEATERS WIRE

(ECO) OF WATER HEATER. LINEAR LIMIT SPILL SWITCH,

30 MILLIVOLT WATER HEATERS REQUIRE USE OF THE

SPILL SWITCH

LINEAR LIMIT

950-0470 (JA1)

THERMOCOUPLE

JUNCTION ADAPTER

SWITCH

J1

UNIVERSAL

CO

NTRO

L

L

E

R

IN THIS APPLICATION. SPILL SWITCH MUST BE INTERLOCKED

WITH HEATING EQUIPMENT AS SHOWN.

SAFETY CIRCUIT ACROSS P1 & P2 OF UC1 IS NOT UTILIZED

R

XN

XL

PRESSURE

WHKE GAS

RED JUMPER POSITION MUST BE THE SAME

AS APPLIANCE INTERLOCK VOLTAGE.

IMPORTANT:

1

15V

J2

CALL
JUMPER

24V

DRY

POWER!

SUPPLY

DO NOT

MILLIVOLT

FIGURE 8050033 3-29-11

BOARD-

POWER.

115 VAC

LEGEND:

5 VDC

GENERATED

GAS

VALVE

FACTORY WIRED TO

L AND N ON DCOP1

Each millivolt appliance interlocked with the UC1 must have its own WHKE kit installed. The WHKE Gas Pressure Switch actuates
the Inducer through the A - B Dry contacts. The Linear Limit switch disables the heater in the event of a venting malfunction.
IMPORTANT: Each millivolt appliance interlocked with the UC1 must have its own Linear Limit spill switch.

1. Wire WHKE Gas Pressure Switch in series with A and B terminal on UC1. Do not supply voltage to A and B terminals.
2. Wire WHKE Linear Limit in series with thermocouple junction adapter or high limit ECO of water heater.
3. Make sure RED voltage jumper on UC1 is in the DRY position.

NOTE: If only venting millivolt appliances the PSA-1 Fan Proving Switch is not required, see WHKE instructions for

complete details.

UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 OR 115 VAC STANDING PILOT

JUMPER

115 VAC

24 OR 115 VAC

XN

XL

J2

J1

LEGEND:

UNIVERSAL CO

NTRO

LLER

AS APPLIANCE INTERLOCK VOLTAGE.

RED JUMPER POSITION MUST BE THE SAME

115V

CALL

24V

DRY

IMPORTANT:

FIGURE 8050032 3-28-11

FACTORY WIRED TO

L AND N ON DCOP1

24V OR 115V GAS VALVE

TR

COM

TH

HOT

INTERNAL CONTROLS

OF FURNACE/BOILER

B2

COM

Aquastat

T-stat

B1

HOT

1. Remove the wire on TH or HOT of gas valve and connect it on #1 on UC1 terminal block.
2. Connect #2 on UC1 terminal block to TR or Common.
3. Connect #4 on UC1 terminal block to TH or HOT on gas valve.
4. Make sure RED voltage jumper on UC1 is on 24V or 115V depending on control voltage.