DCOP1 INSTALLATION

Do not mount the DCOP1 junction box on a heat source that exceeds 140

O

F (60

O

C). Examples of improper mounting surfaces

include vent pipe, top of heater casing or any place where radiant or convective heat would cause the junction box temperature to
exceed 140

O

F (60

O

C). The DCOP1 is intended for indoor installation only.

Using the key hole slots on the back of the DCOP1 junction box as a template, mark 4 holes on the mounting surface, drill pilot
holes if necessary, and secure junction box using provided screws.

ELECTRICAL WIRING

P1 & P2 PRE-CYCLE FAN PROVER STATUS CHECK

Pre-Cycle
Prover Status
Check Deactivated

The Pre-Cycle Prover Status Check is deactivated from the factory. When activated, the UC1
Universal Control checks across P1 & P2 safety circuit (PSA-1 Fan Prover) to verify that the Fan
Prover switch is “Open” upon a call for heat and not stuck “Closed”. Natural draft or winds may be
sufficient to close the PSA-1 Fan Prover switch contacts prior to a call for heat. Keeping the Prover
Status Check activated may cause nuisance lockouts. Push dip switch 9 up or “ON” to deactivate.

9

ON

PRE-PURGE SETTINGS (SEE “PRE-PURGE” ON PAGE 3 PRIOR TO SETTING)

1 2

1 2

1 2

1 2

0 Seconds

5 Seconds

20 Seconds

35 Seconds

EXAMPLE OF DCOP1

& ROOFTOP INDUCER

INSTALLED WITH

MULTIPLE HEATERS

POST-PURGE SETTINGS (SEE “POST-PURGE” ON PAGE 3 PRIOR TO SETTING)

4

3

4

8

6

5

7

3

5 6 7 8

3 4 5 6 7 8

3

7

5

4

6

8

4

3

4

8

6

5

7

3

5 6 7 8

3 4 5 6 7 8

4 Minutes

8 Minutes

16 Minutes

1 Minute

0 Seconds

30 Seconds

2 Minutes

ON

ON

Pre-Purge

Post-Purge

Pre-Cycle
Prover Status
Check Deactivated

DIP SWITCH NUMBERING

1

ON

2

3 4

5 6

7 8

9