INSTALLATION PROCEDURES

3-16

NOTE: The dryer must be isolated from the gas supply piping system by closing its individual

manual shut off valve during any pressure testing of the gas supply piping system at test

pressures equal to or less than 1/2 psig (3.5 kpa).

Figure.3-10 Typical of Gas Installation

Piping must be installed in accordance with good commercial steam system practice. Care

must be exercised when leveling steam dryers in final position. After leveling the dryer, check the
downward pitch of the heat exchanger from front to rear with a level. Likewise, check the
downward pitch of the return condensate manifold toward its outlet part. Absence of these
downward pitches will result in probable water hammer and premature heat exchanger fracture and
leakage.

The presence of condensate in the steam will cause water hammer and subsequent heat

exchanger failure. The steam supply connection must be taken from the top of a well-dripped steam
main. If the supply run-out to the dryer exceeds 20 feet, it should be dripped just before the control
valve with a proper trap and dirt pocket.

It is your responsibility to have ALL steam plumbing connections made by a qualified

professional to assure that the installation is adequate and conforms with local and state regulations
or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in

component failure which will VOID THE WARRANTY.

1. Steam Requirements High Pressure

Inlet ---- 2-inch supply line connection.
Return --- 2-inch return line connection.

G. STEAM INFORMATION

MAIN GAS SUPPLY TANKS

HIGH PRESSURE 0-300PSI

PRESSURE

RELIEF VALVE

HIGH PRESSURE

GAUGE 0-300PSI

PRESSURE GAUGE 0-60PSI

MEASURING 7PSI (0.48BAR)

HIGH PRESSURE

REGULATOR

GAS SUPPLY LINE 7PSI

LOW PRESSURE

SECOND STAGE

GAS REGULATOR

MAX INLET PRESSURE

10PSI (0.69BAR)

OUTLET PRESSURE

12-14 INCHES WC. (LPG)

4.5-14 INCHES WC. (NG)

GAS DRYER MACHINE

WITH GAS VALVE MAX INLET

PRESSURE 0.5PSI BUT IF USE

SECOND STAGE REGULATOR

WITH 11 INCHER WC. 0.41PSI (LPG)

4 INCHES WC.0.145 PSI (NG)