B&C Technologies DP-250 Industrial User Manual

Page 31

Advertising
background image

INSTALLATION PROCEDURES

3-17

Table 3-4 Steam Requirements High Pressure

Operating Steam Pressure

Maximum 125

psig

Minimum 100

psig

Heat Input (Normal Load)

27 Bhp

Consumption (Approximate)

800 lbs/hr

2. Installation Instructions

To insure that an adequate supply of steam is provided, be sure that the steam supply and

steam return lines are sized and laid out as stipulated in this manual. Inadequate steam supply and
steam return lines or improper steam plumbing will result in poor performance and can cause
component failure. Clean, dry, regulated steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE
WARRANTY.

The presence of condensate in the steam supply will cause water hammer and subsequent

heat exchanger failure. The steam supply connection into the main supply line must be made with a
minimum 10” riser. This will prevent any condensate from draining towards the dryer.

The steam supply piping to the dryer must include a 12" rise along with a drip trap and

check valve. This will prevent any condensate from entering the steam coil.

Flexible hoses or couplings must be used. The dryer vibrates slightly. when it runs, and this

will cause the steam coil connections to crack if they are hard piped to the supply and return mains.

Shut-off valves for each dryer should be installed in the supply, return, and drip trap return

lines. This will allow the dryer to be isolated from the supply and return mains if the dryer needs
maintenance work.

Install a float and thermostatic steam trap and check valve at least 12” below steam coil as

near to the coil as possible.

A vacuum breaker should be installed in the piping. This will prevent the condensing steam

from causing a vacuum inside the coil and possibly damaging the coil.

The supply and return lines should be insulated. This will save energy and provide for the

safety of the operator and maintenance personnel.

Water pockets in the supply line, caused by low points, will provide wet steam to the coil

possibly causing coil damage. All horizontal runs of steam supply piping should be pitched ¼”
every foot back towards the steam supply header, causing any condensate in the line to drain to the.
Header. Install a bypass trap in any low point to eliminate wet steam.

Do not

elevate the condensate return line after the float and thermostatic trap. Drain only by

gravity into a properly vented low pressure return line or condensate tank.

Advertising
This manual is related to the following products: