4 connection to dc power supply – CANOGA PERKINS 9101 LAN Chassis User Manual

Page 19

Advertising
background image

19

9101 LAN Chassis

Canoga Perkins

The polarity of the source DC supply is fixed and therefore determines the appro-
priate connection to the 9101 DC terminals.

If a -48 VDC supply is indicated, the strap is connected from the Chassis Ground to
the +VDC terminal. Then the positive (+) or Common lead from the source DC
supply and the negative (-) lead from the source DC supply are connected to like
terminals on the 9101 power entry barrier strip.

Figure 3-8

9101 LAN Chassis Alarm Contacts

3.4 Connection to DC Power Supply

The connections for typical -48VDC and +48VDC power supplies are shown in
Figure 3-9.

-VDC

Terminal for negative lead

CHS-GND

Chassis ground terminal for DC supply

+VDC

Terminal for positive lead

The chassis alarm contacts are illustrated in Figure 3-8. The interpretation of the
alarms are as follows:

Norm Open

Open during normal operation / closed during a power fault
condition.

Common

The common pin between alarm contacts.

Norm Clsd

Closed during normal operation / open during a power fault
condition.