c. Measure time (in sec) for gas meter to complete 1

revolution and note reading. The 2 or 5 cubic feet dial

provides a more accurate measurement of gas flow.

d. Refer to Table 12 for cubic ft. of gas per hr.

e. Multiply gas rate (cu ft./hr) by heating value (Btuh/cu ft.)

to obtain input.

If clocked rate does not match required input from Step 1,

increase manifold pressure to increase input or decrease manifold
pressure to decrease input. Repeat steps b through e until correct

input is achieved. Reinstall regulator seal cap on gas valve.

5. Set temperature rise. The furnace must operate within the

temperature rise ranges specified on the furnace rating
plate. Do not exceed temperature rise range specified on

unit rating plate. Determine the temperature rise as
follows:

NOTE: Blower access door must be installed when taking
temperature rise reading. Leaving blower access door off will
result in incorrect temperature measurements.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
Disconnect 115--v electrical power before changing speed

tap.

!

WARNING

a. Place thermometers in return and supply ducts as close

to furnace as possible. Be sure thermometers do not see
radiant heat from heat exchangers. Radiant heat affects

temperature rise readings. This practice is particularly
important with straight--run ducts.

b. When thermometer readings stabilize, subtract return--air

temperature from supply--air temperature to determine air
temperature rise.

NOTE:

Blower access door must be installed for proper

temperature rise measurement.
NOTE: If the temperature rise is outside this range, first check:

(1.) Gas input for heating operation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50--in. wc.

(4.) Dirty filter.

c. Reinstall blower access door if removed.

d. Turn gas valve ON/OFF switch to ON.

e. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise

f. Turn thermostat down below room temperature and

remove blower access door.

g. To change motor speed selection for heating, remove

blower motor lead from control HEAT terminal (See Fig.
24.) Select desired blower motor speed lead from one of

the other terminals and relocate it to the HEAT terminal
(See Table 11 for lead color identification). Reconnect

original lead to SPARE terminal.

h. Repeat steps a through e.

i. When correct input rate and temperature rise is achieved,

turn gas valve ON/OFF switch to OFF.

j. Remove manometer or similar device from gas valve.

k. Reinstall manifold pressure tap plug in gas valve.

A06666

Fig. 52 -- Gas Control Valve

BURNER

ORIFICE

A93059

Fig. 53 -- Orifice Hole

FIRE HAZARD
Failure to follow this warning could result in personal

injury, death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent

gas leak.

!

WARNING