Table 5 — 50RTG04 Blower Performance

LEGEND

NOTES:

1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.

Table 6 — 50RTG05 Blower Performance

LEGEND

NOTES:

1. Fan BHP includes drive losses.
2. Region “A” is standard drive package.
3. Regions “B” and “C” require optional drive packages.
4. Region “D” represents oversized motor and special sheaves.
5. For applications requiring higher static pressures, contact your local representative.

SCFM

AIRFLOW

EXTERNAL STATIC PRESSURE (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1300

BHP

0.26

0.30

0.33

0.36

0.40

0.42

RPM

633

694

755

812

869

925

Turns Out

5

3.5

4.5

3.5

2.5

1.5

1400

BHP

0.33

0.36

0.40

0.43

0.46

0.50

0.53

Operation Not Recommended

RPM

668

725

782

836

890

943

995

Turns Out

4

3.0

4.0

3.0

2.0

1.0

0.5

1500

BHP

0.418

0.45

0.48

0.52

0.55

0.58

0.62

0.65

RPM

712

766

819

871

922

970

1017

1063

Turns Out

3.0

4.5

3.5

2.5

1.5

0.5

3.5

3.0

1600

BHP

0.506

0.54

0.57

0.61

0.64

0.67

0.70

0.75

0.78

0.83

RPM

750

801

851

900

948

995

1040

1083

1125

1166

Turns Out

4.5

3.5

3.0

2.0

1.0

0.0

3.5

1.5

2.0

1.5

1700

BHP

0.572

0.62

0.66

0.70

0.74

0.78

0.81

0.86

0.89

0.94

RPM

792

840

887

934

979

1024

1068

1110

1152

1194

Turns Out

4.0

3.0

2.0

1.5

0.5

3.5

3.0

2.5

1.5

1.0

1800

BHP

0.671

0.72

0.76

0.80

0.85

0.89

0.94

0.97

1.01

1.06

RPM

832

878

923

967

1010

1053

1095

1136

1176

1219

Turns Out

3.0

2.5

1.5

1.0

0.0

3.0

2.5

2.0

1.5

1.0

1900

BHP

0.80

0.85

0.89

0.94

0.98

1.02

1.07

1.11 1.16

1.20

RPM

875

919

961

1003

1045

1086

1127

1166

1204

1242

Turns Out

2.5

1.5

1.0

0.0

3.0

2.5

2.0

1.5

1.0

0.5

BHP

Brake Horsepower

SCFM — Standard Cubic Feet Per Minute

SCFM

AIRFLOW

EXTERNAL STATIC PRESSURE (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1700

BHP

0.37

0.42

0.45

0.50

0.54

0.58

0.63

0.67

Operation Not

Recommended

RPM

797

845

892

938

984

1029

1072

1114

Turns Out

3.5

2.5

1.5

3.0

2.5

1.5

1.0

0.5

1800

BHP

0.44

0.48

0.53

0.56

0.61

0.65

0.70

0.75

0.79

RPM

836

882

927

971

1015

1057

1099

1140

1180

Turns Out

2.5

1.5

3.5

2.5

2.0

1.0

0.5

0.5

0.0

1900

BHP

0.52

0.56

0.61

0.65

0.69

0.74

0.78

0.84

0.88

0.94

RPM

880

923

966

1008

1049

1090

1131

1170

1208 1246

Turns Out

1.5

3.5

3.0

2.0

1.5

0.5

0.5

0.0

3.0

2.5

2000

BHP

0.61

0.65

0.69

0.74 0.78

0.84

0.88

0.94

0.98

1.03

RPM

926

967

1007

1047

1087

1126

1164

1203

1240

1277

Turns Out

3.5

3.0

2.0

1.5

1.0

0.5

0.0

3.0

2.5

2.0

2100

BHP

0.69

0.74

0.78

0.84

0.88

0.94

0.98

1.03

1.09

1.14

RPM

966

1005

1044

1082

1120

1158

1195

1231

1268

1303

Turns Out

3.0

2.0

1.5

1.0

0.5

0.0

3.0

2.5

2.0

1.5

2200

BHP

0.79

0.84

0.89

0.94

0.99

1.05

1.09

1.14 1.20

1.25

RPM

1009

1047

1084

1120

1157

1193

1229

1264

1298

1333

Turns Out

2.0

1.5

1.0

0.5

3.5

3.0

2.5

2.0

1.5

1.0

2300

BHP

0.9

0.96

1.00

1.06

1.11

1.17

1.22

1.28

1.33

1.39

RPM

1055

1091

1126

1161

1196

1231

1265

1299

1332

1365

Turns Out

1.0

4.5

4.0

3.5

3.0

2.5

2.0

1.5

1.0

0.5

BHP

Brake Horsepower

SCFM — Standard Cubic Feet Per Minute

D

A

B

C

D

A

B

C

Advertising