Step 3 — location of unit – Carrier 50RTG User Manual

Page 3

Advertising
background image

3

INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:

1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the
correct unit has been shipped.

2. Verify that the unit is the correct model for the entering

water temperature of the job.

3. Do not remove the packaging until the unit is ready for

installation.

4. Verify that the refrigerant tubing is free of kinks or dents,

and that it does not touch other unit components.

5. Inspect all electrical connections. Be sure connections are

clean and tight at the terminals.

6. Compressors are internally spring-mounted. Compressors

equipped with external spring vibration isolators must
have bolts loosened and shipping clamps removed.

7. Remove any blower support cardboard from inlet of the

blower if present.

8. Locate and verify any accessory kit located in compressor

section.

9. Remove any access panel screws that may be difficult to

remove once unit is installed.

Step 3 — Location of Unit —

The following guide-

lines should be considered when choosing a location for
WSHP. Refer to Fig. 1 and 2 for unit dimensional data:
• Provide sufficient space for water, electrical and duct

connections

• Locate unit in an area that allows for easy access and

removal of filter and access panels

• Allow enough space for service personnel to perform

maintenance

Table 1 — Physical Data — Aquazone™ 50RTG03-20 Units

UNIT 50RTG

03

04

05

07

08

10

12

15

20

OPERATING WEIGHT (lb)

735

785

835

880

1080

1125

1175

1770

1960

SHIPPING WEIGHT (lb)

750

800

850

900

1100

1150

1200

1800

2000

REFRIGERANT TO AIR HEAT EXCHANGER

Face Area (sq ft)

5

5

5

7.5

9.3

9.3

10.5

20

20

Rows Deep

2

3

3

3

3

3

3

4

4

Copper Tube Size (in.)

3

/

8

3

/

8

3

/

8

3

/

8

3

/

8

3

/

8

3

/

8

3

/

8

3

/

8

No. Fins per Inch

12

12

12

12

12

12

12

12

12

REFRIGERANT CHARGE R-22/Ckt (oz)

52

68

86

132

68

86

88

141

160

NUMBER OF CIRCUITS

1

1

1

1

2

2

2

2

2

BLOWER DATA

Diameter (qty-in.)

1-10

1-10

1-10

1-12

1-15

1-15

1-15

2-15

2-15

Width (in.)

6

6

10

11

11

11

11

11

11

FILTER DATA

Size (in.)

16 x 20

16 x 20

16 x 20

16 x 20

16 x 20

16 x 20

16 x 20

16 x 20

16 x 20

Quantity

4

4

4

4

6

6

6

10

6