Carrier AQUAZONE 50PEC09-18 User Manual

Page 19

Advertising
background image

19

LEGEND

NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 115-V (WHT) lead for

115/1/60 units, 265-V (BRN) lead for 265/1/60
units, 240-V (ORG) lead for 240/1/50 units, or
208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is
230-1-60 or 220-1-50, insulate unused lead.

4. FP1 thermistor provides freeze protection for

WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.

5. Refer to LonWorks† Installation, Application, and

Operation manual for control wiring to the unit.
Low voltage wiring must be “class 1” and voltage
rated equal to or greater than unit supply
voltage.

6. Factory-cut jumper (JW1). Dry contact will be

available between AL1 and AL2.

7. Transformer secondary ground via Complete C

board standoffs and screws to control box.
(Ground available from top 2 standoffs as
shown.)

AL

—

Alarm Relay Contacts

BM

—

Blower Motor

BR

—

Blower Relay

CAP

—

Capacitor

CB

—

Circuit Breaker

CO

—

Sensor, Condensate Overflow

CR

—

Compressor Relay

DM

—

Damper Motor

FP1

—

Sensor, Water Coil Freeze Protection

FP2

—

Sensor, Air Coil Freeze Protection

FSS

—

Fan Speed Switch

HP

—

High-Pressure Switch

JW1

—

Jumper Wire for Alarm

LOC

—

Loss of Charge Pressure Switch

PB

—

Power Terminal Block

RVS

—

Reversing Valve Solenoid

TRANS —

Transformer

WV

—

Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring
Option Low-Voltage Wiring
Printed Circuit Trace

*Optional wiring.

†Registered trademark of Echelon Corporation.

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

COMPLETE C

COMPLETE C

PEC

PEC12-18

PEC

a50-8327.eps

Fig. 18 — 50PEC Unit with Complete C and LON Controllers