OPTIONAL WALL-MOUNTED THERMOSTAT — The

50PEC water source heat pump units are built with standard in-

ternal thermostats in either manual changeover (MCO) or auto-

matic changeover (ACO) configuration. Refer to Fig. 17-20.

When desired, the unit can be furnished with a 24-v control

circuit which is field wired to a Carrier-supplied accessory re-

mote thermostat. Most heat pump thermostats can be used with

the controller. Use a thermostat with Y, G, O and W outputs.

Refer to unit wiring diagrams in Fig. 21 and 22 and Aquazone

Controls, Operation, and Troubleshooting Instructions for addi-

tional information.

Vendor installation instructions and additional installation

information is shipped with each thermostat.
NOTE: Low-voltage wiring between the unit and the wall ther-

mostat must comply with all applicable electrical codes

(i.e., NEC and local codes), and be completed before the unit is

installed.

Table 3 lists recommended wire sizes and lengths to install

the thermostat. The total resistance of low-voltage wiring must

not exceed 1 ohm. Any resistance in excess of 1 ohm may

cause the control to malfunction because of high voltage drop.

Table 3 — Recommended Thermostat Wire Sizes

*Length = Physical distance from thermostat to unit.

OPTIONAL PREMIERLINK™ CONTROLLER — This di-

rect digital controller (DDC) allows the water source heat

pump to be incorporated into a Carrier Comfort Network

®

(CCN) system installation. PremierLink control is factory-

installed with the Complete C controller, or field-installed with

the Deluxe D control option. Refer to Fig. 23 and 24.
WSHP OPEN WIRING — The WSHP Open controller will

be factory wired to the Complete C or Deluxe D control board,

however, the system wiring will need to be completed utilizing

WSHP Open controller wiring diagrams and the Third Party

Integration (TPI) Guide. Factory installation includes harness,

LWT (leaving water temperature), supply air, and condensate

sensor.

Wiring Sensors to Inputs — Sensors can be wired to the

WSHP Open controller’s inputs. See Table 4.
All field control wiring that connects to the WSHP Open con-

troller must be routed through the raceway built into the corner

post. The raceway provides the UL required clearance between

high and low-voltage wiring.

1. Pass control wires through the hole provided in the corner

post.

2. Feed the wires through the raceway to the WSHP Open

controller.

3. Connect the wires to the removable Phoenix connectors.
4. Reconnect the connectors to the board.

Field-Supplied Sensor Hardware — The WSHP Open con-

troller is configurable with the following field-supplied sen-

sors. See Table 4.

Table 4 — Field-Supplied Sensors for

WSHP Open Controller

NOTE: BACview

6

Handheld or Virtual BACview can be used as the

user interface.

For specific details about sensors, refer to the literature sup-

plied with the sensor.
Wiring a SPT Sensor — A WSHP Open controller is connect-

ed to a wall-mounted space temperature (SPT) sensor to moni-

tor room temperature using a Molex plug.

The WSHP Open system offers the following SPT sensors.

See Table 5.

Table 5 — SPT Sensors

*The SPT Pro Plus fan speed adjustment has no effect in this

application.

Wire SPT sensors to the WSHP Open controller’s Rnet port.

An Rnetbus can consist of any of the following combinations

of devices wired in a daisy-chain configuration:
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

• 1 to 4 SPT Standard sensors

• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or

SPT Pro Plus sensor

• Any of the above combinations, plus up to 2 BACview

6

Handheld but no more than 6 total devices

NOTE: If the Rnetbus has multiple SPT Standard sensors, each

sensor must be given a unique address on the Rnetbus. See the

Carrier Open Sensor Installation Guide.
Use the specified type of wire and cable for maximum signal

integrity. See Table 6.

WIRE SIZE

MAX WIRE LENGTH*

18-Gage

75 ft

16-Gage

125 ft

14-Gage

200 ft

WARNING

Disconnect all power to the unit before performing mainte-

nance or service. Unit may automatically start if power is

not disconnected. Failure to follow this warning could

cause personal injury, death, and/or equipment damage.

SENSOR

NOTES

Space Temperature Sensor

(SPT)

Field Installed (Must be used with

WSHP Open controller.)

Outdoor Air

Temperature Sensor

Network Sensor

Indoor Air Quality Sensor

(Separate Sensor)

Required only for demand

control ventilation.

Space Relative Humidity

Sensor

Separate Sensor

SENSOR

PART

NUMBER

FEATURES

SPT

Standard

SPS

• Local access port
• No operator control

SPT Plus

SPPL

• Slide potentiometer to adjust set point
• Manual on button to override schedule
• LED to show occupied status
• Local access port

SPT Pro

SPP

• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set

point

• Info button to cycle through zone and

outside air temperatures, set points, and
local override time

• Local access port

SPT Pro

Plus

SPPF

• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set

point

• Info button to cycle through zone and

outside air temperatures, set points, and
local override time

• Local access port
• Fan speed*