Deluxe d – Carrier AQUAZONE 50PEC09-18 User Manual

Page 21

Advertising
background image

21

*Optional wiring.

AL

— Alarm Relay Contacts

BM

— Blower Motor

BR

— Blower Relay

CAP

— Capacitor

CB

— Circuit Breaker

CO

— Sensor, Condensate Overflow

CR

— Compressor Relay

DM

— Damper Motor

FP1

— Sensor, Water Coil Freeze Protection

FP2

— Sensor, Air Coil Freeze Protection

HP

— High-Pressure Switch

JW1

— Jumper Wire for Alarm

LOC

— Loss of Charge Pressure Switch

NLL

— Night Low Limit Switch

PB

— Power Terminal Block

RAS

— Return Air Sensor

RVS

— Reversing Valve Solenoid

TRANS

— Transformer

WV

— Water Valve

----------

Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace

LEGEND

Relay/Contactor Coil

Solenoid Coil

Thermistor

Circuit Breaker

Relay Contacts-N.O.

Switch-Temperature

Switch-High Pressure

Switch-Low Pressure

Ground

Wire Nut

Mate-N-Lock

>>

NOTES:

1. Compressor and blower motor thermally pro-

tected internally.

2. All wiring to the unit must comply with local

codes.

3. Transformer is wired to 115-V (WHT) lead for

115/1/60 units, 265-V (BRN) lead for 265/1/60
units, 240-V (ORG) lead for 240/1/50 units, or
208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is
230-1-60 or 220-1-50, insulate unused lead.

4. FP1 thermistor provides freeze protection for

WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.

5. Refer to Microprocessor Control Installation,

Application, and Operation manual for control
wiring to the unit. Low voltage wiring must be
“class 1” and voltage rated equal to or greater
than unit supply voltage.

6. Factory-cut jumper (JW4). Dry contact will be

available between AL1 and AL2.

7. Transformer secondary ground via Deluxe D

board standoffs and screws to control box.
(Ground available from top 2 standoffs as
shown.)

DELUXE D

DELUXE D

PEC09-18

a50-8329

Fig. 20 — 50PEC Unit Manual or Auto Changeover and Deluxe D Controller