APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)

LEGEND

SCREEN NAME

POINT NAME

PASSWORD

LEVEL

EDITABLE

RANGE

DEFAULT

NOTES

Unit

Maintenance

Operating Mode

No Password

required

Off, Fan Only,Economize,

Cooling, Heating, Cont Fan, Test,

Start Delay, Dehumidify

Displays unit operating mode

Fan Operating Mode

Auto/Continuous/Always On

Displays how the fan is configured

to operate

Occupancy Status

Unoccupied/Occupied

Displays the current occupancy status

Occupancy Control

Always Occupied/Local Schedule/

BACnet Schedule/BAS Keypad/

Occupied Contact/Holiday Schedule/

Override Schedule/Pushbutton

Override/Unoccupied None

Displays the origin of the

occupancy control

Outside Air

Temperature

F

Displays OAT (Viewable only if OAT

is a network broadcast)

SPT

F

Displays SPT

SPT Status

Normal/Above Limit/Below

Limit/Sensor Failure

Displays the SPT status

SPT Sensor Status

Inactive/Connected

Displays the connection status

of the Rnet sensor

Condensate Overflow

Normal/Alarm

Displays the status of the

condensate overflow

Cooling Set Point

F

Displays the actual set point

being used for cooling control

Heating Set Point

F

Displays the actual set point

being used for heating control

Set Point Adjustment

F

Displays the offset values from the Rnet

user set point adjustment that is being

applied to the configured set points

Auxiliary Heat Control

Set Point

F

Displays the calculated set point being

used for auxiliary heating control

H

2

O Economizer

Control Set Point

F

Displays the calculated set point being

used for economizer control

Calculated IAQ/

Ventilation Damper

position

%

Displays the ventilation damper

position calculated by the DCV control

Active Compressor

Stages

0/1/2

Displays the actual number of

compressor stages operating

SAT

F

Displays SAT

Reset Filter Alarm

X

No/Yes

Used to reset the filter alarm timer after

the filter has been cleaned or replaced

Overflow Contact

Closed/Open

Displays the state of the condensate

overflow switch contact

Occupancy Contact

Closed/Open

Displays the state of the external/

remote occupancy input switch contact

BAS/Keypad Override

X

Inactive/Occupied/

Unoccupied

Inactive

Provides capability to force the

equipment to operate in an

occupied or unoccupied mode

OAT Input

N/A / Network

Displays if an OAT value is being

received from the Network

System Settings

BACnet

X

See TPI

Keypad Configuration

X

Mapping

Password

X

Changes password

Network

X

See TPI

BACnet Time Master

X

See TPI

Clock Set

X

Changes clock/time setting

Occupancy

Maintenance

Override Schedules

No Password

required

Inactive/Active Occupied

Used to display the active and

inactive occupancy control inputs

Pushbutton Override

Inactive/Active Occupied

Keypad Override

Inactive/Active Occupied/Active

Unoccupied

Schedules

Inactive/Active Occupied

Occupancy Contact

Inactive/Active Occupied

BAS on/off

Inactive/Active Occupied

Schedule

Configuration

Local Occupancy

Schedules

User/Admin

Password level

access

X

Disable/Enable

Enable

Used to define which occupancy inputs

are used to determine

occupancy mode.

Local Holiday

Schedules

X

Disable/Enable

Disable

Local Override

Schedules

X

Disable/Enable

Disable

BACnet Occupancy

Schedules

X

Disable/Enable

Disable

°
°

°

°

°

°

°

°

BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration