AAF International Millennium User Manual

Page 5

Advertising
background image

5. When the caulking has been applied, and before it dries, join the

modules and bolt them together, placing the bolts and washers in

every hole provided. Tighten the bolts fully.

6. Repeat the procedure described in Section 3.3, steps 3 through 5,

until all of the modules have been connected.

NOTE: Depending on the availability of space, the ability to

maneuver equipment, and the size of the collector, it may be

necessary to modify this erection procedure. This may be done

at the discretion of the rigging contractor after thoughtful

consideration and consultation with an AAF representative.

3.4 Ductwork

Connect the inlet duct to the drilled and flanged inlet(s) of the

collector. Connect the clean air duct to the drilled collector outlet.

Ductwork should be of sufficient gauge to withstand the system

design pressure and should be independently supported. The

Millennium is not designed to support ductwork. Hot gas ducts

may require expansion joints to prevent expansion loads on collector

inlets and outlets.
Close coupling a duct elbow to the collector inlet will result in an

uneven velocity profile. This condition may result in less than optimum

collector performance. A straight run of duct with a length equal to

three to four duct diameters immediately before the inlet will provide

an adequate airflow distribution to the inlet.
When attaching inlet and outlet ducts, caulk the flanges appropriately

to ensure that no leakage will occur during operation.
3.5 Ladder and Handrail Assembly

It is necessary to install the access ladder and handrails after

assembling the collector. The first step is to position the handrails

into place and secure them with bolts at the posts. The kick plates

are integral to the handrail sections. Refer to the installation drawings

supplied with the equipment for details.

The access ladder assembly is complete with a safety cage and

mounting brackets. Bolt (or weld) the ladder to the collector housing,

as shown in the installation drawing. The ladder assembly has

mounting brackets which attach to the housing and to the

hopper/housing flange. Ladder mounting brackets may be

bolted (or field welded) to the collector.
3.6 Electrical Controls and Wiring

WARNING: Potential shock hazard. Disconnect power before

servicing. Only qualified electrical personnel should work on

this system.

The standard Millennium dust collector is supplied with electrical

solenoid valves mounted in a NEMA 4 enclosure installed adjacent

to the pressure manifold, and a pulse/timer control (normally one

control system is supplied for a complete unit). As previously

mentioned, a number of control and wiring options are available

with the Millennium. In lieu of the standard offering, your Millennium

may be supplied with a pressure demand control, or NEMA 9 rated

solenoid enclosures. Consult the contract drawings for details.
Always mount the control enclosure in an accessible location.

Control wiring must then be field installed between the solenoid

valves in the enclosure adjacent to the pressure manifold and the

timer output terminals in the control enclosure, as shown on the

electrical connection diagram. Refer to the drawing supplied with

the equipment for details. All electrical wiring material and labor will

be supplied by others.

Figure 5.

Control Board

without module

Control Board

with module

5

Figure 4

Bolt Hole

Sealant Bead

Housing or Hopper Flange

Advertising