Appendix a – AERCO BMS 168 User Manual

Page 52

Advertising
background image

A-4

Appendix A

(cont.)

________________________


DEFAULT VALUES

System State

Halted (stop mode)

Header Set Mode

Indoor/Outdoor Reset

Indoor Air Input

Thermistor

Boiler Op Mode

Sequential

Start Level

45%

Stop Level

18%

Auxiliary Relay Open

45% Fire Rate

Auxiliary Relay Close

100% and Off

Header Temperature Bandwidth 70°F
Integral Gain

.15 repeats/min.

Derivative Gain

.15

System Start Relay

70°F

Building Reference Temperature 70°F
Header Reference Temperature 160°F
Header High Limit

220°F

Header Low Limit

40°F

Reset Ratio

1.2

Indoor Setpoint

70°F

All Offset Temperatures

0

All Offset Times

0

Indoor Prop Band

0

Maximum Power Input

100%

Interlock 1

Start Enabled

Number of Combo Units

1

Real-Time Clock

Set to Present Date and Time