Appendix a – AERCO BMS 168 User Manual
Page 52
Advertising

A-4
Appendix A
(cont.)
________________________
DEFAULT VALUES
System State
Halted (stop mode)
Header Set Mode
Indoor/Outdoor Reset
Indoor Air Input
Thermistor
Boiler Op Mode
Sequential
Start Level
45%
Stop Level
18%
Auxiliary Relay Open
45% Fire Rate
Auxiliary Relay Close
100% and Off
Header Temperature Bandwidth 70°F
Integral Gain
.15 repeats/min.
Derivative Gain
.15
System Start Relay
70°F
Building Reference Temperature 70°F
Header Reference Temperature 160°F
Header High Limit
220°F
Header Low Limit
40°F
Reset Ratio
1.2
Indoor Setpoint
70°F
All Offset Temperatures
0
All Offset Times
0
Indoor Prop Band
0
Maximum Power Input
100%
Interlock 1
Start Enabled
Number of Combo Units
1
Real-Time Clock
Set to Present Date and Time