Table H1 Error Messages - Continued

Fault Message

Description & Possible cause

SYSTEM ERROR,

INTERLOCK 2 OPEN

Interlock 2 is open

(4-20 MA) INPUT

OPEN LOOP ERROR

The 4-to-20-mA remote input signal has dropped below 3 mA, or the

signal is not present at the BMS.

FAIL SAFE MODE

ACTIVATED

This message can be displayed when the BMS is controlling the

boilers via Modbus or PWM communication. It indicates that the BMS

is operating in the Fail Safe (Constant Setpoint) mode.

NETWORK COMM FLT

TIMEOUT ERROR

Displayed during Modbus Remote Setpoint operation when the BMS is

functioning as a Slave to an EMS Master. Error indicates that the

Network Timeout has expired.

NETWORK DISABLED

MODBUS LISTEN

Displayed during Modbus operation when the “FORCE LISTEN

ONLY” Modbus diagnostic command is sent to the BMS Slave by the

controlling Master, thereby disabling normal Modbus Network

communication. It indicates that the Master is listening for the

“RESTART COMMUNICATIONS OPTIONS” diagnostic command

required to restart normal Modbus communication. The BMS will

operate in the Fail Safe mode during this period.