Appendix h - troubleshooting, Appendix h – AERCO BMS 168 User Manual

Page 71

Advertising
background image

H-1

Appendix H

_____________________________

TROUBLESHOOTING

When a fault occurs in the boiler plant, the BMS flashes error messages at 2-second intervals

and the alarm contacts close. To cancel alarms (open contacts but message still displays),

press the RESET RATIO key The fault messages shown in Table H1 can occur in any mode of

operation, Constant Setpoint, Indoor/Outdoor Reset, or Remote Setpoint. Some of the most

common problems encountered in BMS operation are contained in Table H2.

Table H1 Error Messages

Fault Message

Description & Possible cause

OUTSIDE AIR TEMP
NOT CONNECTED

• Open outside air temp. sensor: resistance greater than 240K ohms

(less than -40°F)

Shorted outside air temp. sensor: resistance less than 1K ohms

(greater than 200°F)

No sensor connected

Note: Displays only in 4-to-20 mA and Constant

Setpoint modes. It does not display as an error message, and

will display only after pressing the AIR TEMP key.

OUTSIDE AIR TEMP

SENSOR ERROR

When in Indoor/Outdoor Reset Mode, the outside air temperature

sensor is either open, shorted, or not connected.

HEADER TEMP

SENSOR ERROR

• Open header sensor: resistance greater than 240K ohms (less than

-40°F)

Shorted header sensor: resistance less than 240 ohms (over

300°F)

Sensor not installed

INDOOR AIR TEMP

SENSOR ERROR

• Open indoor air temp. sensor: resistance greater than 240K ohms

(less than -40°F) .

Shorted sensor: resistance less than 240 ohms (over 300°F)

No sensor installed and Prop Band is adjusted to > 0°F/°F

SYSTEM ERROR,
INTERLOCK 1

Interlock 1 is open