C-1
Appendix C
_____________________________
Normal (Read-Only) Mode
Display Messages and Defaults
Key Display
Message
Default Range
HDR
TEMP
HEADER TEMP
160°F
(Default Display)
(Press and Hold) HEADER SET TEMP
160°F
160°F
40 to 220°F
AIR
TEMP
OUTSIDE AIR TEMP
70°F
(Press and Hold) INDOOR AIR TEMP
70°F
(If Connected)
% LOAD
PERCENT OF LOAD
100% 8 Units
100 %
0 to 100 %
0 to 40 Units
SYS
START TEMP
(Press and Hold)
SYS. START RELAY
70°F
70°F
32 to 120°F
REF
TEMP
(Press and Hold)
BLDG REF TEMP
(Indoor/Outdoor Reset Mode)
70°F
40 to 220°F
HEADER REF. TEMP
(Constant Setpoint Mode)
120°F
40 to 220°F
BLDG
REF
TEMP
(Remote Setpoint Mode)
70°F
40 to 220°F
HDR
TEMP
LIMIT
(Press and Hold)
HDR HIGH LIMIT
220°F
220°F
40 to 220°F
SET
POINT
(Press and Hold)
INDOOOR SET POINT
70°F
70°F
50 to 150°F
PROP
BAND
(Press and Hold)
INDOOR PROP BAND
00.0°F/°F
00.0°F/°F
0 to 20°F/°F
in 0.5°F/°F
increments
RESET
RATIO
(Press and Hold)
RESET RATIO
1.2°F/°F
(Indoor/Outdoor Reset Mode
Only)
1.2°F/°F
0.3 to 3.0°F/°F
in 0.1 increments
FUNCTION NOT VALID
(All Other Modes)
OFF
SET
(Press and Hold)
OFFSET TEMP
0°F
0°F
-50 to +50°F