Appendix c - normal mode display messages, Appendix c – AERCO BMS 168 User Manual

Page 61

Advertising
background image

C-1

Appendix C

_____________________________


Normal (Read-Only) Mode

Display Messages and Defaults

Key Display

Message

Default Range

HDR

TEMP

HEADER TEMP
160°F
(Default Display)

(Press and Hold) HEADER SET TEMP

160°F

160°F

40 to 220°F

AIR

TEMP

OUTSIDE AIR TEMP
70°F

(Press and Hold) INDOOR AIR TEMP

70°F
(If Connected)

% LOAD

PERCENT OF LOAD
100% 8 Units

100 %

0 to 100 %

0 to 40 Units

SYS

START TEMP

(Press and Hold)

SYS. START RELAY
70°F

70°F

32 to 120°F

REF

TEMP

(Press and Hold)

BLDG REF TEMP
(Indoor/Outdoor Reset Mode)

70°F

40 to 220°F

HEADER REF. TEMP
(Constant Setpoint Mode)

120°F

40 to 220°F

BLDG

REF

TEMP

(Remote Setpoint Mode)

70°F

40 to 220°F

HDR

TEMP

LIMIT

(Press and Hold)

HDR HIGH LIMIT
220°F

220°F

40 to 220°F

SET

POINT

(Press and Hold)

INDOOOR SET POINT
70°F

70°F

50 to 150°F

PROP
BAND

(Press and Hold)

INDOOR PROP BAND
00.0°F/°F

00.0°F/°F

0 to 20°F/°F

in 0.5°F/°F

increments

RESET

RATIO

(Press and Hold)

RESET RATIO
1.2°F/°F
(Indoor/Outdoor Reset Mode
Only)

1.2°F/°F

0.3 to 3.0°F/°F

in 0.1 increments

FUNCTION NOT VALID
(All Other Modes)

OFF

SET

(Press and Hold)

OFFSET TEMP
0°F

0°F

-50 to +50°F