Appendix j, Table j-1. bms commands – AERCO BMS 168 User Manual

Page 80

Advertising
background image

Appendix J

(cont.)

__________________________


Table J-1. BMS COMMANDS


No.


COMMAND


ENTRY RANGE

FACTORY

DEFAULT

21

Aux Relay Mode

0 = 100% Fire Rate
1 = 100% and OFF

1 = 100% AND OFF

22

Temperature Sensor Fail Mode

0 = Shutdown
1 = Switch Inputs

0 = Shutdown

23

Fault Relay Mode

0 = All Faults
1 = No Interlock
2 = Interlock 2
3 = Interlock 1

0 = All Faults

24

Alarm Clear Method

0 = Automatic
1 = Manual

0 = Automatic

25

Boiler Operation Mode

0 = Parallel
1 = Sequential
2 = Combination

1 = Sequential

26

Number Of PWM Combo Units

0 to 4

1

27
28
29


Reserved

30

Maximum PWM Percent Level

50 to 100

100

31

Interlock 1 Method Of Operation

0 = Always Enabled
1 = Start Enabled

1 = Start Enabled

32

Real Time Clock - Minutes

00 to 59

Present Time

33

Real Time Clock - Hours

00 to 23

Present Time

34

Real Time Clock - Day Of Week

1 to 7

Present Day

35

Real Time Clock - Year

00 to 99

Present Year

36

Real Time Clock - Day Of Month

00 to 31

Present Day

37

Real Time Clock - Month

00 to 12

Present Month

38 (Day

1)

Thru

Offset Temperatures (Day 1-7)

-50 to +50°F

All Set To 0°F

44 (Day

7)

J

-

4