Appendix j, Table j-1. bms commands – AERCO BMS 168 User Manual
Page 80

Appendix J
(cont.)
__________________________
Table J-1. BMS COMMANDS
No.
COMMAND
ENTRY RANGE
FACTORY
DEFAULT
21
Aux Relay Mode
0 = 100% Fire Rate
1 = 100% and OFF
1 = 100% AND OFF
22
Temperature Sensor Fail Mode
0 = Shutdown
1 = Switch Inputs
0 = Shutdown
23
Fault Relay Mode
0 = All Faults
1 = No Interlock
2 = Interlock 2
3 = Interlock 1
0 = All Faults
24
Alarm Clear Method
0 = Automatic
1 = Manual
0 = Automatic
25
Boiler Operation Mode
0 = Parallel
1 = Sequential
2 = Combination
1 = Sequential
26
Number Of PWM Combo Units
0 to 4
1
27
28
29
Reserved
30
Maximum PWM Percent Level
50 to 100
100
31
Interlock 1 Method Of Operation
0 = Always Enabled
1 = Start Enabled
1 = Start Enabled
32
Real Time Clock - Minutes
00 to 59
Present Time
33
Real Time Clock - Hours
00 to 23
Present Time
34
Real Time Clock - Day Of Week
1 to 7
Present Day
35
Real Time Clock - Year
00 to 99
Present Year
36
Real Time Clock - Day Of Month
00 to 31
Present Day
37
Real Time Clock - Month
00 to 12
Present Month
38 (Day
1)
Thru
Offset Temperatures (Day 1-7)
-50 to +50°F
All Set To 0°F
44 (Day
7)