Table H2 Common Problems

Problem

Possible Causes

Solution

Boiler plant not started
by BMS

• Outside air temperature

higher than system’s start

temperature

• System must be initialized

• Wiring between boilers and

BMS not correct

• Check outside air temperature and

system start temperature. System

start temperature should be higher

than outside air temperature for

boilers to run. See para. 4.3.3 and

4.3.5.

Initialize and test system (para. 5.5

and 5.6).

• Check wiring (Section 3)

Boiler not being
recognized by BMS with
Modular Control Box

• Temperature controller is

not in Manual/Remote

mode



• Temperature controller’s

secure menu is not locked

• Boilers are not correctly

addressed

Wiring between the BMS

and boilers is incorrect

Indoor sensor not installed

but value has been entered

under PROP BAND

• Check temperature controller. The

REM and MAN lights should be

illuminated. If not, shut off AC

power to the boiler, wait 30 sec.,

and reapply power. The boiler will

automatically return to

remote/manual mode.

• Go to Secure menu in temperature

controller. It should display Secure

3. If the display shows Secure 4,

relock to Secure 4.

• See para. 5.4

• See Section 3 for correct wiring

connections

• If value has been entered under

PROP BAND, change value to

00/00° F

Boiler not being
recognized by BMS with

C-More Control Box

• C-More Box not configured

correctly.

• C-More Box not enabled.

Front panel switch is off.

• Incorrect wiring between

BMS and Boiler.

• Ensure that the C-More Boiler is

configured for Direct Drive and

PWM (see para. 5.5 of GF-109

(KC1000) or GF-110 (Benchmark)

for required menu settings.

• Check ON/OFF switch.

• See Section 3 for correct wiring

connections