INSTALLATION

2-4

SHELL DRAIN

VALVE

EXHAUST

MANIFOLD

REAR VIEW

A

A

B

B

CONDENSATE

TRAP

DRAIN

CONNECTING

MANIFOLD

DRAIN

UNIT

FRAME

CONNECTING

MANIFOLD

DRAIN

VALVE

CONDENSATE

DRAIN PIPE

TO

CONDENSATE

TRAP

SHELL

VIEW “B - B”

VIEW “A - A”

UNIT

FRAME

EXHAUST

MANIFOLD

CONDENSATE

TRAP

DRAIN

HOSE

CLAMP

1" I.D.

HOSE

TO FLOOR

DRAIN

Figure 2-5

Condensate Drain Connection Location

2.6.1 Exhaust Manifold Condensate

Drain

Refer to Figure 2-5, View A – A and install as

follows:
1. Connect a length of 1 inch I.D. hose (part no.

91030) to the drain on the exhaust manifold

and secure it in place with a hose clamp.

2. Route the hose to a nearby floor drain.

2.6.2 Connecting Manifold Condensate

Drain

The connecting manifold drain pipe shown in

Figure 2-5, View B – B must be connected to a

separate condensate drain trap external to the

unit. This condensate trap (part no. 24060) is

supplied with the unit along with a trap adapter

and a 3/4” NPT x 5” long nipple. Refer to Figure

2-6 and install the trap as follows:

NOTE

The condensate trap described in the

following steps can be installed on the

floor behind the unit as shown in Figure 2-

6. Ensure that the condensate trap inlet is

level with or below the connecting

manifold drain pipe. Ensure that the outlet

hose from the trap slopes away (down)

from the trap.

1. Apply Teflon tape to the threads of the 3/4” x

5” long nipple provided with the boiler.

2. Attach the 3/4” NPT nipple between the

condensate trap inlet and the trap adaptor

(Figure 2-6).

3. Attach another 3/4” NPT nipple (not sup-

plied) to the condensate trap outlet on the

lower part of the trap.

4. Connect the condensate trap and adaptor to

the connecting manifold drain pipe. Position

the trap so it is level and then tighten the

thumb screw on the adaptor.

5. Place a suitable support under the

condensate trap to maintain the trap in the

level position.

6. Connect a length of 1” I.D. polypropylene hose

to the outlet side of the condensate trap and

route it to a nearby floor drain.


If desired, a Tee fitting may be used to connect the

two drain hoses from the exhaust manifold and the

outlet side of the of the condensate trap attached to

the connecting manifold.
If a floor drain is not available, a condensate pump

can be used to remove the condensate to drain.

The maximum condensate flow rate is 20

GPH.

The condensate drain trap, associated fittings and

drain lines must be removable for routine

maintenance.

CONDENSATE

TRAP

CONNECTING

MANIFOLD

DRAIN

PIPE

3/4" NPT

NIPPLES

TO

FLOOR

DRAIN

CLAMP

1" I.D.

HOSE

ADAPTOR

Figure 2-6

Condensate Trap Installation