Installation – AERCO BMK 3.0 LN Natural Gas July 2011 User Manual

Page 23

Advertising
background image

INSTALLATION

2-11









Diagram 2-1b: Schematic – System Pump

Start using a Separate Contact Relay

Figure 2-12: Identifying the Presence of BMK

Pump Relay Option 69102

2.11 AUXILIARY RELAY CONTACTS

Each Boiler is equipped with a single pole

double throw (SPDT) relay that is energized

when there is a demand for heat and de-

energized after the demand for heat is satisfied.

The relay is provided for the control of auxiliary

equipment, such as pumps and louvers, or can

be used as a Boiler status indictor (firing or not

firing). Its contacts are rated for 120 VAC @ 5

amps. Refer to Figure 2-11 to locate the AUX

RELAY terminals for wiring connections.

2.12 FLUE GAS VENT INSTALLATION

The minimum allowable vent diameter for a

single Benchmark 3.0 Boiler is 8 inches.
The AERCO Benchmark Venting and

Combustion Air Guide, GF-2050, must be

consulted before any flue gas vent or inlet air

venting is designed or installed. U/L listed,

positive pressure, watertight vent materials as

specified in AERCO’s GF-2050, must be used

for safety and code compliance. Since the unit is

capable of discharging low temperature exhaust

gases, horizontal sections of the flue vent

system must be pitched back to the unit a

minimum of 1/4 inch per foot to avoid

condensate pooling and allow for proper

drainage.
The combined pressure drop of vent and

combustion air systems must not exceed 140

equivalent feet of 8 inch ducting. Fittings as well

as pipe lengths must be calculated as part of the

equivalent length.
For a natural draft installation the draft must not

exceed ±0.25 inch W.C. These factors must be

planned into the vent installation. If the

maximum allowable equivalent lengths of piping

are exceeded, the unit will not operate properly

or reliably.
For Massachusetts boiler installations, the

Heatfab Division of the Selkirk Corporation

provides vent systems which conform to all

applicable requirements for installations within

the Commonwealth of Massachusetts. Contact

information for this supplier is as follows:
Selkirk Corporation

Heatfab Division

130 Industrial Blvd.

Turners Falls, MA 01376

Phone: 1-800-772-0739

www.heat-fab.com

2.13 COMBUSTION AIR

The AERCO Benchmark Venting and Combus-

tion Air Guide, GF-2050 MUST be consulted

before any flue or combustion supply air venting

is designed or implemented. Combustion air

supply is a direct requirement of ANSI 223.1,

NFPA-54, CSA B149.1 and local codes. These

codes should be consulted before a permanent

design is determined.
The combustion air must be free of chlorine,

halogenated hydrocarbons, or other chemicals

that can become hazardous when used in gas-

fired equipment. Common sources of these

compounds are swimming pools, degreasing

compounds, plastic processing and refrigerants.

Whenever the environment contains these types

of chemicals, combustion air must be supplied

from a clean area outdoors for the protection

and longevity of the equipment.
The AERCO Benchmark 3.0 Boiler is UL listed

for 100% sealed combustion. It can also be

installed using room air, provided there is an

adequate supply. (See paragraph 2.13.3 for

more information concerning sealed combustion

air). If the sealed combustion air option is not

Advertising