INSTALLATION

2-12

being used, an inlet screen will be attached at

the air inlet on the top of the unit
The more common methods of supplying

combustion air are outlined below. For more

information concerning combustion air, consult

the AERCO Benchmark Venting and

Combustion Air Guide, GF-2050.

2.13.1 Combustion Air From Outside the

Building

Air supplied from outside the building must be

provided through two permanent openings. Each

opening must have a free area of not less than

one square inch for each 4000 BTU/H boiler

input. The free area must take into account

restrictions such as louvers and bird screens.

For Canada installations, refer to the

requirements specified in CSA B149.1-10, 8.4.1

and 8.4.3.

2.13.2 Combustion Air From Inside the

Building

When combustion air is provided from within the

building, it must be supplied through two

permanent openings in an interior wall. Each

opening must have a free area of not less than

one square inch per 1000 BTU/H of total boiler

input. The free area must take into account any

restrictions such as louvers.

2.13.3 Sealed Combustion

The AERCO Benchmark 3.0 Boiler is UL listed

for 100%-sealed combustion. For sealed

combustion installations, the screen on the air

inlet duct of the unit must be removed. The inlet

air ductwork must then be attached directly to

the unit’s air inlet.

In a sealed combustion air application, the

combustion air ducting pressure losses must be

taken into account when calculating the total

maximum allowable venting run. See the

AERCO Benchmark Venting and Combustion

Air Guide, GF-2050. When using the boiler in a

sealed combustion air configuration, each unit

must have a minimum 8-inch diameter

connection at the unit.

2.13.4 Temporary Combustion Air

Filtering During Construction

When the AERCO Benchmark 3.0 Boiler is used

to provide heat temporarily during ongoing

building construction, accumulated drywall dust,

sawdust and similar particles can accumulate in

the unit’s combustion air intake filter and block

combustion air flow. In these situations, AERCO

recommends that a disposable air intake filter be

installed, temporarily, above the boiler

combustion air inlet.

AERCO recommends that the temporary air filter

be cut from a McMaster-Carr part no. 2122K315

Polyester Air Filter Roll Tackfield, 1/2” thick, 16”

wide, or equivalent. Cover the Benchmark 3.0

air inlet with the blue side of the filter material

facing outward to hold the dust on the outside

surface. Maximize the surface area of the filter

covering the 8" diameter opening by creating a

dome out of the filter material.
During construction, check the filter for dust

accumulation and replace it when the

accumulation becomes noticeable.